4. Refrigerant Piping Installation
4.1  Length  and  Drop  Height  Requirements  for  the  Piping 
Connections to the Indoor and Outdoor Units
The length and drop height requirements for the refrigerant piping are different 
for  different  indoor  and  outdoor  units.  Refer  to  the  installation  manual  of  the 
outdoor unit.
4.2 Piping Material and Size
1.  Piping material: Copper pipes for air handling.
2.  Piping  size:  Choose  and  purchase  copper  pipes  that  correspond  to  the 
length and size calculated for the selected model in the installation manual 
of the outdoor unit and your actual project requirements.
4.3 Piping Layout
1.  Seal the two ends of the piping properly before you connect the indoor and 
outdoor  piping.  Once  unsealed,  connect  the  piping  of  the  indoor  and 
outdoor  units  as  quickly  as  possible  to  prevent  dust  or  other  debris  from 
entering the  piping system via the unsealed  ends, as  this may cause the 
system to malfunction.
2.  If  the  piping  needs  to  go  through  walls,  drill  the  opening  in  the  wall,  and 
place accessories like casings and covers for the opening properly.
3.  Place the refrigerant connecting piping and the communication wiring for the 
indoor and outdoor units together, and bundle them tightly to make sure air 
does not enter and condensate to form water that may leak from the system.
4.  Insert the bundled piping and wiring from outside the room through the wall 
opening 
into  the  room.  Be  careful  when  you  lay  out  the  piping.  Do  not 
damage the piping.
4.4 Piping Installation
  Refer to the installation manual attached with the outdoor unit on installation 
of the refrigerant piping for the outdoor unit.
  All gas and liquid piping must be properly insulated; otherwise, this may cause 
water to leak. Use heat insulation materials that can withstand high tempera-
tures above 120°C to insulate the gas pipes. In addition, the insulation of the 
refrigerant piping should be reinforced (20 mm or thicker) in situations where 
there is high temperature and/or high humidity (when part of refrigerant piping 
part is higher than 30°C or when the humidity exceeds RH80%). Otherwise, 
the surface of the heat insulation material may be exposed.
  Before the works are carried out, verify that the refrigerant is R410A. If the 
wrong refrigerant is used, the unit may malfunction.
  Other than the specified refrigerant, do not let air or other
 gases enter the 
refrigeration circuit.
  If the refrigerant leaks during installation, make sure you fully ventilate the room.
  Use  two  wrenches  when  you  install  or  dismantle  the  piping,  a  common 
wrench and a torque wrench. See Figure 4.1.
 
 
•  Apply  the  appropriate  tightening  torque  according  to  the  installation 
conditions. Excessive torque will damage the socket cap, and the cap will 
not be tight if you apply insufficient torque, leading to leakages.
4.5 Air Tightness Test
Carry out the air tightness test on the system according to the instructions in the 
installation manual of the outdoor unit.
4.7 Vacuum
Create a vacuum in the system according to the instructions in the installation 
manual of the outdoor unit.
4.8 Refrigerant
Charge  the  system  with  refrigerant  according  to  the  instructions  in  the 
installation manual of the outdoor unit.
 
 
4.6 Heat Insulation Treatment for Gas-Liquid Piping Connections 
for the Indoor Unit
  The heat insulation treatment is carried out on the piping at the gas and liquid 
sides of the indoor unit respectively.
a.  The piping on the gas side must use heat insulation material that can 
withstand temperatures of 120°C and more.
b.  For the piping connections of the indoor unit, use the insulation casing 
for  copper  pipes  (accessory  6)  to  carry  out the insulation  treatment, 
and close all gaps.
Unit 
body
Attached insulation 
heat pump belt
On-site 
piping side
Face upwards
Figure 4.5
Figure 4.1
Torque wrench
Pipe socket cap
Pipe fittings
Normal wrench
  Slot the refrigerant piping into the brass nut (accessory 13), and expand the 
pipe socket. Refer to the following table for the size of the pipe socket and 
the appropriate tightening torque.
Figure 4.2
External diameter
 (mm)
Tightening 
torque
Figure 4.3
Apply refrigerant oil
  Before the socket cap is installed on the pipe socket, apply some refrigerant 
oil on the socket (both inside and outside), and then rotate it three or four 
times before you tighten the cap. See Figure 4.3.
Precautions to take when welding the refrigerant pipes
•  Before you weld  the  refrigerant pipes, fill  the  pipes with nitrogen  first  to 
discharge the air in the pipes. If no nitrogen is filled during welding, a large 
amount of oxide film will form inside the piping which may cause the air 
conditioning system to malfunction.
•  Welding can be carried out on the refrigerant pipes when the nitrogen gas 
has been replaced or refilled.
•  When the pipe is filled with nitrogen during welding, the nitrogen must be 
reduced to 0.02 MPa using the pressure release valve. See Figure 4.4.
Figure 4.4
•  The Air Tightness Test helps to ensure that the air and liquid cut-off 
valves of the outdoor unit are all closed (maintain the factory defaults).
 
 
 
•  For the vacuum, make sure that the air and liquid cut-off valves of the 
outdoor unit are all closed (maintain the factory status).
 
 
 
Caution
Caution
R0.4~0.8
A
45°±  2
90°± 4
Flared opening
diameter (A)
Flared opening
Φ6.35 14.2-17.2N·m 8.3-8.7mm
Φ9.53 32.7-39.9N·m 12-12.4mm
Φ12.7 49.5-60.3N·m 15.4-15.8mm
Φ15.9 61.8-75.4N·m 18.6-19mm
Φ19.1 97.2-118.6N·m 22.9-23.3mm
Caution
Fi
ure 4.4
1 Copper piping
2 Section being brazed
3 Nitrogen connection
4 Hand valve
5 Pressure-reducing valve
6 Nitrogen
9