Figure 5.1
Slope of 1/100 
or more
Figure 5.3
  Before the test, make sure that the water discharge pipeline is smooth, and 
check that each connection is sealed properly.
  Conduct the water discharge test in the new room before the ceiling is paved.
1.  Remove the test water cap to connect to the test water outlet, and use the 
water injection pipe to inject 2000 ml of water into the drain pan.
5.2 Water Discharge Test
Water suction pipe
Test water outlet
Body
Drain pan
Test water cap
Water injection pipe
Water discharge trench
Figure 5.2
•
 
Make sure all the connections in the piping system are properly sealed 
to prevent water leakages.
6.  When connecting to a long water discharge pipe, the connections must be 
covered  with  the  insulation  casing  to  prevent  the  long  pipe  from  coming 
loose.
7.  When the outlet of the water discharge pipe is higher than the pipe connec-
tion for  water suction, try  to keep the  water discharge pipe  as vertical as 
possible, and the water outlet connecting fittings will bend so that the height 
of the water discharge pipe should be within 1000 mm away from the base 
of the drain pan. Otherwise,  there  will  be  excessive  water flow when the 
operation stops. See Figure 5.2.
Water discharge pipes from multiple units are connected to the main 
water discharge pipe to be discharged through the sewage pipe.
Water outlet 
pipe fittings
Main water 
outlet pipe
Slope of 
1/100 or more
Below 200 mm
All are below 1000 mm
Below 200 mm
Below 200 mm
8.  If the end of the water discharge pipe is more than 50mm above the ground 
or from the base of the water discharge slot, do not put it in the water.
2.  Connect the power supply, and set the air conditioner to operate in the cool 
mode. Check the running sound of the drainage pump, as well as whether 
water is properly drained from the water discharge outlet.
3.  Stop the air conditioner. Wait for three minutes, and then check if there is 
anything unusual. If the water discharge piping layout is not correct, the 
excessive water flow will cause the water level error and “EE” error code will 
be displayed on the display panel. There may even be water overflowing 
from the drain pan.There may even be water overflowing from the drain pan.
4.  Continue to add water until the alarm for excessive water levels is triggered. 
Check if the drainage pump drains water immediately. After three minutes, 
if  the  water  level  does  not  fall  below  the  warning  level,  the  unit  will  shut 
down. At this time, you need to turn off the power supply, and drain away the 
accumulated water before you can turn on the unit normally.
5.  Turn off the power supply, remove the water manually using the drainage 
plug, and put the test cap back to the original place.
 
•  The drainage plug at the bottom of the unit body is used to discharge 
accumulated  water  from  the  drain  pan  when  the  air  conditioner 
malfunctions.  When  the  air  conditioner  is  operating  normally,  make 
sure  the  drainage  plug  is  properly  plugged  to  prevent  water  from 
leaking.
5. Water Discharge Piping Installation
5.1. Water Discharge Piping Installation for Indoor Unit
1.  Use PVC pipes for the water discharge pipes (outer diameter: 37~39 mm, 
inner  diameter:  32  mm).  Based  on  the  actual  installation  circumstance, 
users can purchase the appropriate piping length from sales agent or local 
after-sales service centre, or purchase directly from the local market.
2.  Insert the water discharge pipe into the end of the water suction connecting 
pipe of the unit body, and use the ring clamp (accessory 10) to clamp the water 
discharge pipes with the insulation casing for the water outlet piping securely.
3.  Use  the  insulation  casing  for  water  discharge  piping  (accessory  9)  to 
bundle the water suction and discharge pipes of the indoor unit (especially 
the indoor portion), and use the tie for the water discharge piping (accesso-
ry 12) to bind them firmly to make sure air does not enter and condense.
4.  In  order  to  prevent  the  back-flow  of  water  into  the  interior  of  the  air 
conditioner  when  the  operation  stops,  the  water  discharge  pipe  should 
slope downwards towards  the outside (drainage  side)  at a slope  of more 
than 1/100. Make sure that the water discharge pipe does not swell or store 
water; otherwise, it will cause strange noises. See Figure 5.1.
5.  When connecting the  water discharge piping, do not use 
force to pull the 
pipes to prevent the water suction pipe connections from coming loose. At 
the same time, set a supporting point at every 0.8~1 m to prevent the water 
discharge pipes from bending. See Figure 5.1.
Caution
50~100mm
50~100mm
50~100mm
Caution
>1.0m
0.8~1.0m
Warning
6. Electrical Wiring
•  All the supplied parts, materials and electrical works must comply with local 
regulations.
•  Use only copper wires.
•  Use a dedicated power supply for the air-conditioners. The power voltage 
must be in line with the rated voltage.
•  The electrical wiring works must be carried out by a professional technician, 
and must comply with the labels stated in the circuit diagram.
•  Before the electrical connection  works  are  carried out, turn  off  the  power 
supply to prevent injuries caused by electric shock.
•  The  external  power  supply  circuit  of  the  air  conditioner  must  include  an 
earth line, and the earth line of the power cord connecting to the indoor unit 
must be securely connected to the earth line of the external power supply.
•  Leakage  protective  devices  must  be  configured  according  to  the  local 
technical standards and requirements for electrical and electronic devices.
•  The fixed wiring connected must be equipped with an all-pole disconnection 
device with a minimum 3 mm contact separation.
•  The distance between the power cord and signalling line must be at least 
300 mm to prevent the occurrences of electrical interference, malfunction or 
damage  to  electrical  components.  At  the  same  time,  these  line  must  not 
come in contact with the piping and valves.
•  Choose  electrical  wiring  that  conforms  to  the  corresponding  electrical 
requirements.
•  Connect to the power supply only after all the wiring and connection works 
have been completed, and carefully checked to be correct.
10