FLA: Full Load Amps
Abbreviations:
MCA: Minimum Circuit Amps
kW: Rated motor output
 
Table 6.2  Indoor units electrical characteristics
MFA: Maximum Fuse Amps 
IFM: Indoor Fan Motor
Table 6.1
Capacity
IFM 
Hz  Volts 
MCA 
MFA  kW  FLA 
2.8kW     
  0.41 
15  0.08  0.33 
  0.41 
15  0.08  0.33 
4.5kW      
  0.56 
15  0.08  0.45 
5.6kW  
0.56 
15  0.08  0.45 
7.1kW    
  0.56 
15  0.08  0.45 
8.0kW    
  0.76 
15  0.08  0.61 
   
  0.88 
15  0.17  0.70 
10.0kW    
1.00 
15  0.17  0.80 
11.2kW    
  1.00 
15  0.17  0.80 
14.0kW    
  1.20 
15  0.17  0.96 
Power supply 
3.6kW
9.0kW
Power supply
Breakers with 
current leakage
All-pole disconnection 
device with leakage 
protector
L  N
Pull box
Indoor unit Indoor unit Indoor unit
Pull boxPull box
220-240V~50/60Hz
: Copper wire
Proper power wiring connections
POWER IN
L
N
Wire slot
Indoor power
supply
Outdoor power
supply
Indoor unit
Communication wire between 
indoor and outdoor units
Grounding line
Grounding line
RCCB
RCCB
Figure 6.1
Figure 6.2
4.6 erugiF3.6 erugiF
 
 
6.1 Power Cord Connection
  Use a dedicated power supply for the indoor unit that is different 
from the power supply for the outdoor unit.
  Use the same power supply, circuit breaker and leakage protective 
device for the indoor units connected to the same outdoor unit.
When connecting to the power supply terminal, use the circular wiring 
terminal with the insulation casing (see Figure 6.3).
If circular wiring terminal with the insulation casing cannot be used,
please make sure that:
•  Do  not  connect  two  power  cords  with  different diameters  to  the 
same power supply terminal (may cause overheating of wires due 
to loose wiring) (See Figure 6.4).
Use power cord that conforms to  the specifications and connect 
the power cord firmly. To prevent the cord from being pulled out by 
external force, make sure it is fixed securely.
Figure 6.2 shows the power supply terminal of the indoor unit.
Refer to Tables 6.1 and 6.2 for the specifications of the power cord 
and  communication  wire.  A  wiring  capacity  that  is  too  small  will 
cause the electrical wiring to become too hot, and lead to accidents 
when the unit burns and becomes damaged.
+
Power cord
Insulation tube
Circular wiring 
terminal
Figure 6.5
6.2 Electrical Wiring Specifications
Warning
Refer  to  local  laws  and  regulations  when  deciding  on  the 
dimensions for the power cords and wiring. Get a professional to 
select and install the wiring.
11
Model 2.8-14.0 kW
Power
supply
 
220-240V~50Hz
220-240V~50/60Hz
Communication wire between
indoor and outdoor units
Shielded  3×AWG16-AWG18
Communication wire between
indoor unit and wired controller
  AWG16-AWG20
Field fuses 15A
Phase
Volt and frequency
1-phase
220-240V~50Hz
Indoor unit
Indoor unit
Pull box
Shielded
*
*
Please refer to the corresponding wired controller manual for the wired
controller wiring.
50/60   
50   
220-240V
1.  Select the wire diameters( minimum value) individually for each 
unit based on the table 6.3. 
2.   Maximum allowable voltage range variation between phases is  
2%.
3.   Select circuit breaker that having a contact separation in all poles 
not less than 3 mm providing full disconnection,where MFA is 
used to select the current circuit breakers and residual current 
operation breakers.
Table 6.3
Nominal cross-sectional area (mm
2
 ) 
 
 
>3  
 >6 
 >10 
 >16 
 >25 
 >32 
 
>50 
and 
and 
and 
and 
and 
and 
and 
≤3 
 ≤6 
≤10 
≤16 
≤25 
≤32 
≤50 
≤63 
 
0.75 
1 
1.5
2.5
4 
  6 
 
10 
and 
and 
and 
and 
and 
and 
and 
1 
1.5 
2.5
4
6 
10
16
0.5   and  0.75
Flexible cords Cable for fixed wiring
4
10
to
1.5
4
to
1
2.5
to
1
2.5
to
1
2.5
to
2.5
6
to
6
16
to
10
25
to
 Rated current 
of appliance(A)