3.2. Indoor Unit Installation
3.2.1 Installation sequence for existing ceiling
3.2.2 Installation sequence for new ceiling
Figure 3.2
Figure 3.5
Figure 3.6
Figure 3.7
Figure 3.3
Figure 3.4
 
 
•  All  bolts  should  be  made  from  high  quality  carbon  steel  (with 
galvanized  surface  or  other  rust  prevention  treatment)  or  stainless 
steel.
•  How the ceiling should be handled will differ with the type of building. 
For  specific  measures,  please  consult  the  building  and  renovation 
engineers.
•  How  the  hoisting  bolt  should  be  secured  depends  on  the  specific 
situation, and it must be secure and reliable.
  Must maintain the ceiling at a level position.
Original concrete slab structure
Steel framework
Newly set concrete slab structure
Use embedded bolts, and pull bolts.
Directly set and use an angled 
steel rod for support.
Set using embedded appliances, 
and embedded type of bolts.
Suspension 
bolt
Angled rod 
for support
Suspension bolt
Knife-type 
insertion piece
Sliding-type insertion piece
Reinforced bar
Embedded bolt
(hanging and embedded 
bolt for piping)
1.  Drill 910x910mm square holes into the ceiling based  on the  layout of  the 
installation board (accessory 4). See Figure 3.5.
  The centre of the ceiling opening should match the centre of the body of the 
indoor unit.
  Determine the length and outlets of the connecting pipes, water discharge 
piping and the electrical wiring.
  In  order  to  keep  the  ceiling  level  and  prevent  vibrations,  reinforce  the 
strength of the ceiling when necessary.
Air conditioner body
Ceiling
Position the hole at the 
centre of the ceiling opening
Piping
Water discharge pipe
2. Install the hooks in four corners based on the layout for the hooks outlined in 
the installation board (accessory 4).
  Determine  the  location  on  the  ceiling  of  the  room  or  building  roof  for 
mounting, and drill four Φ12mm X 50-55 mm holes. Then embed and set up 
the expansion hook anchors (purchased accessory 4) in these holes. See 
Figure 3.2.
  During  the  installation  of  the hooks  (purchased  accessory  5),  make  sure 
that the concave portion of the hanger corresponds to that of the expansion 
hook anchors. Determine the appropriate hook length for installation based 
on the ceiling's height. Remove any excess.
Use M10 or W3/8/ bolts for the screws of the mounting hooks.
Take approximately 1/2 of the screw length for the installed hooks as the 
excess length.
Top
3.  Use the hex nuts on the four mounting hooks to adjust and make sure that 
the unit body is level.
  If the water discharge pipe is slanted, it may cause the water level switch to 
malfunction, and water may leak.
  Adjust the  position of the unit body,  and make sure that the  gap with  the 
ceiling is evenly spaced on all four sides of the ceiling, and the base of the 
unit body is 10-12 mm into the base of the ceiling.
Once the position of the unit body is adjusted, use the nuts on the mounting 
hooks to secure the unit.
1.  Refer to Step 2 of the "Installation sequence for existing ceiling". Pre-bury 
the hooks in the new ceiling, and make sure that they are strong enough to 
bear the weight of the indoor unit, and that the unit will not become loose 
when the concrete shrinks.
2.  Once you have lifted and mounted the unit, use M6x12 screws (accessory 
5) to secure the installation board (accessory 4) on the unit body. Make sure 
you verify the size and positions of the opening in the ceiling before you do 
so. See Figure 3.8.
  Before you mount the unit onto the ceiling, make sure the ceiling is level.
  The  rest  of  the  procedures  are  the  same  as  Step  2  of  the  "Installation 
sequence for existing ceiling".
3.  Refer to Step 3 of the "Installation sequence for existing ceiling".
4.  Remove the installation board (accessory 4).
Air conditioner body
Ceiling
Air conditioner 
body
Air 
conditioner 
frame
Caution
10~12mm
910mm
910mm
5