8.2.4 Refrigerant Leakage Detection diagnosis and solution(EC) 
Malfunction decision 
conditions 
Define the evaporator coil temp.T2 of the compressor just starts 
running as Tcool.   
In the beginning 5 minutes after the compressor starts up, if T2 
<Tcool-2℃  does not    keep continuous 4 seconds and this 
situation happens 3 times, the display area will show “EC” and   
AC will turn off.   
●  T2 sensor faulty 
●  Indoor PCB faulty 
●  System problems, such as leakage or blocking. 
Check cool air blowing out 
from indoor air outlet
Yes
Yes
Check if T2 sensor
No
Check  leakage of system
No
Power off, then restart the 
unit 2 minutes later.
Replace indoor PCB.
Yes
Repair the leakage and 
recharge the refrigerant.
Yes
check blockIng of system and 
clear the blocking