DOUBLE-CHECK PIPE CONNECTIONS
During operation, the pressure of the
refrigerant circuit will increase. This may
reveal leaks that were not present during your
initial leak check. Take time during the Test
Run to double-check that all refrigerant pipe
connection points do not have leaks. Refer to
Gas Leak Check section for instructions.
5.
After the Test Run is successfully completed,
and you confirm that all checks points in List
of Checks to Perform have PASSED, do the
following:
a.
Using remote control, return unit to
normal operating temperature.
b.
Using insulation tape, wrap the indoor
refrigerant pipe connections that you
left uncovered during the indoor unit
installation process.
IF AMBIENT TEMPERATURE IS BELOW 17°C
You can’t use the remote controller to turn
on the COOL function when the ambient
temperature is below 17°C. In this instance,
you can use the MANUAL CONTROL button
to test the COOL function.
1.
Lift the front panel of the indoor unit, and
raise it until it clicks in place. Use suspension
bars to prop up the panel.
2.
The MANUAL CONTROL button is located
on the right-hand side of the display box.
Press it two times to select the COOL
function. See Fig.8.1
3.
Perform Test Run as normal.
Fig. 8.1
Test Run
Manual control button
Suspension bar