Are the high pressure 
switch and main control 
boar wired correctly?
Method: Disconnect the plug. 
Measure the resistance of the 
high pressure protector, if 
the protector is normal the 
value is o, Does a problem 
still exist?
Yes
Yes
Connect high pressure switch 
and mian control board
No
Replace high pressure protectorNo
 Is  the high 
pressure protector 
broken?
Is the outdoor ambient 
temperature is higher than 
50 ?
No
Stop the unit Yes
Check if the outdoor unit 
ventilation is good
Yes
Ensure that the outdoor unit 
ventilation is functioning properly
Is the heat exchanger dirty?
No
Clean the heat exchangerYes
Check whether the refrigerant 
system is functioning properly
 Replace outdoor main 
board. Is the problem 
resolved?
No
P6/J5 displayed
High pressure protection 
Is the outdoor fan running 
properly?
please refer to the solution of fan 
speed has been out of control 
malfunction . Find out the cause and 
have it solved.
No
Yes
NO