MLCAC-UTSM-2010-10 Troubleshooting
Outdoor Units 89
10.1.2 Troubleshooting
For compact 4-way cassette(12K)
NO. Malfunction Running lamp Timer lamp Defrosting lamp Alarm lamp
1
Communication malfunction between indoor and
outdoor units.
X X X
2 Open or short circuit of T1 temperature sensor X X X
3 Open or short circuit of T2 temperature sensor X X X
4 Full-water malfunction X X X
5 Indoor EEPROM malfunction X X
6 IPM module protection X X O
7 Open or short circuit of T3 or T4 temperature sensor O X X
8 Outdoor unit voltage protection O X O
9 Outdoor unit over-current protection X
10 Top temperature protection of compressor X O X
O(light) X(off) (flash at 2.5Hz) (flash at 0.5Hz)
For ceiling & floor(12K),
NO. Malfunction Running lamp Timer lamp Defrosting lamp Alarm lamp
1
Communication malfunction between indoor and
outdoor units.
X X X
2 Open or short circuit of T1 temperature sensor X X X
3 Open or short circuit of T2 temperature sensor X X X
4 Full-water malfunction X X X
5 Indoor EEPROM malfunction X X
6 IPM module protection X X O
7 Open or short circuit of T3 or T4 temperature sensor O X X
8 Outdoor unit voltage protection O X O
9 Outdoor unit over-current protection X
10 Top temperature protection of compressor X O X
O(light) X(off) (flash at 5Hz) (flash at 0.5Hz)
For Duct type(12K)
NO. Malfunction
Running
lamp
Timer
lamp
Defrosting
lamp
Alarm
lamp
Display(nixie
tube)
1
Open or short circuit of T1 temperature
sensor
X X X E0
2
Open or short circuit of T2 temperature
sensor
X X X E1
3
Communication malfunction between indoor
and outdoor units.
X X X E2
4 Full-water malfunction X X X E3
5 Indoor EEPROM malfunction X X E4
6 IPM module protection X X O E5
7
Open or short circuit of T3 or T4 temperature
sensor
O X X E6
8 Outdoor unit voltage protection O X O P0
9 Compressor temperature protection X O X P1
10 Outdoor unit over-current protection X P2
O(light) X(off) (flash at 5Hz)