Handling of the unit
The angle of inclination should not be more than 15º when
carrying the unit, to avoid overturn of the unit.
a. Rolling handling: several rolling rods of the same size are
placed under the base of the unit, and the length of each
rod must be more than the outer frame of the base and
suitable for balancing of the unit.
b. Lifting: the strength lifting rope (belt) can bear should be
4 times the weight of the unit. Check the lifting hook and
ensure that it is firmly attached to the unit, and the lifting
angle should be more than 60º. Any person is not allowed to
stand below the unit when lifting it.
14
11.2 Information requirements for air-to-air conditioners
Information requirements for air-to-air conditioners
Power consumption in modes other than "active mode"
Other items
Model(s):MOUA-96HD1N1-R
Test matching indoor units from1,Duct:MHC-96HWD1N1(A)
Outdoor side heat exchanger of air conditioner:air
Indoor side heat exchanger of air conditioner:air
Type:compressor driven
If applicable:driver of compressor:electric motor
Tj=+35℃
Tj=+30℃
Tj=+25℃
Tj=+20℃
Tj=+35℃
Tj=+30℃
Tj=+25℃
Tj=+20℃
EERd
EERd
EERd
EERd
2.13
3.92
5.57
7.80
-
-
-
-
28.000
20.632
13.263
8.078
kW
kW
kW
kW
Item Symbol Value UnitItem
Rated cooling
capacity
Degradation co-efficient
for air conditioners(*)
Declared cooling capacity for part load at given outdoor
temperatures Tj and indoor 27/19℃ (dry/wet bulb)
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary
energy factor for part load at given outdoor temperatures Tj
P
rated,c
P
dc
P
dc
P
dc
P
dc
C
dc
0.25 -
28 kW
Seasonal space cooling
energy efficiency
η
s,c
187.8
%
Symbol Value Unit
Off mode
Thermosat-off
mode
Crankcase heater
mode
Standby mode
0.040
0.040
kW
kW
0.040
0
kW
kW
P
OFF
P
CK
P
SB
P
TO
Capacity control
Contact details
(*)If Cdc is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25
Where information relates to multi-split air conditioners,the test result and performance data may be obtained on the basis of
performance of the outdoor unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer
Sound power
level,outdoor
GWP of the
refrigerant
For air-to-air air
conditioner:air
flow rate,outdoor
measured
9800- m
3
/h
variable
77
2088
dB
kg CO
2 eq
(100years)
L
WA
Cooling mode: