MCAC-RTSM-2015-01 60Hz R410a ClimaMaster Tropical Rooftop Package Unit
43
10. Electrical Data
10.1 Electrical Data
220v/3Ph/60Hz
Model
Power Supply
Compressor
Evaporator fan motor
Condenser fan motor
MCA
TOCA
MFA
STC
RNC
IPT
Qty
RNC
IPT
Qty
RNC
IPT
Qty
MRBT-60CWN1-D
34.1
34.2
50
115
20
5.85
1
3.85
0.6
1
1.67
0.23
1
MRBT-062CWN1-D
49
58
80
203
30.7
8.569
1
6
1.871
1
4.1
1.1
1
MRCT-062EWN1-D
49
58
80
203
30.7
8.569
1
6
1.871
1
4.1
1.1
1
MRBT-075CWN1-D
49
58
80
203
30.7
8.6
1
6.4
2.1
1
4.1
1.1
1
MRCT-075EWN1-D
49
58
80
203
30.7
8.6
1
6.4
2.1
1
4.1
1.1
1
MRBT-075HWN1-D
49
58
80
203
30.7
8.6
1
6.4
2.1
1
4.1
1.1
1
MRBT-085CWN1-D
52
61
85
203
32.9
9.957
1
5.4
1.6
1
4.1
1.11
1
MRCT-085EWN1-D
52
61
85
203
32.9
9.957
1
5.4
1.6
1
4.1
1.11
1
MRBT-100CWN1-D
65
76
109
267
43.6
11.2
1
6.4
2.1
1
4.1
1.1
1
MRCT-100EWN1-D
65
76
109
267
43.6
11.2
1
6.4
2.1
1
4.1
1.1
1
MRBT-100HWN1-D
65
76
109
267
43.6
11.2
1
6.4
2.1
1
4.1
1.1
1
MRBT-125CWN1-D
81
105
132
163
40.2
6.7
2
11.7
3
1
4.1
1.1
1
MRBT-150CWN1-D
111
119
172
203
61.4
17.2
2
26
3.6
1
8.2
2.22
2
MRCT-150EWN1-D
111
119
172
203
61.4
17.2
2
26
3.6
1
8.2
2.22
2
MRBT-150HWN1-D
111
119
172
203
61.4
17.2
2
26
3.6
1
8.2
2.22
2
MRBT-175CWN1-D
112
121
178
203
65.8
19.9
2
17.3
5.2
1
8.2
2.22
2
MRCT-175EWN1-D
112
121
178
203
65.8
19.9
2
17.3
5.2
1
8.2
2.22
2
MRBT-200CWN1-D
144
156
231
267
87.6
20.6
2
26
5.5
1
18
5.4
2
MRCT-200EWN1-D
144
156
231
267
87.6
20.6
2
26
5.5
1
18
5.4
2
MRBT-200HWN1-D
144
156
231
2 67
87.6
20.6
2
26
5.5
1
18
5.4
2
MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A) STC: Starting Current (A)
RNC: Running Current (A) IPT: Input (kW)
Note:
1. These data are based on the following conditions:
Evaporator Air Input Temperature 85°F DB, 66 °F WB.
Condenser Air Input Temperature 115°F DB.
2. The starting current is indicated for each compressor motor.
3. The maximum currents of the compressor can be estimated as follows.
One compressor unit
Two compressor unit
Max. current
RNC×Max. IPT×/IPT
RNC×Max. IPT×/IPT
Max. instantaneous current
STC
STC+RNC×0.5×Max. IPT×/IPT
Max. IPT×: Compressor power input from the performance table at the expected maximum condition
STC, IPT, RNC: Compressor data from the above table
4. The data in the compressor motor column shall indicate the respective values of the refrigeration cycle.
the voltage imbalance is to be <2% between phases.