5) Outdoor fan motor didn’t run.
6) Four ways valve didn’t work.
Detect if the voltage of compressor which
corresponds to the interface on PCB is 208 ~ 230V
AC between CN6 of OFAN1,OFAN2 and N.
Detect if the fuse on PCB is burned off.
If the outdoor fan motor contactor is
close.
Replace outdoor
fan motor.
Check if the secondary voltage
transformer is normal.
Detect if the voltage is 208 ~ 230V AC
between CN28, CN29 and C on PCB.
Replace four way valve or coil.
Detect if the fuse on PCB is burned off.
Check if the secondary voltage
transformer is normal.