6. Electrical data
Model
Power Supply
Compressor
Eva.Fan Motor
Con. Fan Motor
MCA
TOCA
MFA
STC
RNC
IPT
Qty
RNC
IPT
Qty
RNC
(Each)
IPT
(Each)
Qty.
MRC-062HWN1-R(C)
23.5
28.9
33.2
75
9.7
5.65
1
7.22
1.62
1
3.65
0.83
1
MRC-075HWN1-R(C)
29.4
36.5
43.7
121.2
14.3
8.08
1
7.18
1.61
1
3.93
0.88
1
MRC-085HWN1-R(C)
29.6
36.3
47.2
62×2
8.8×2
5.13×2
2
2.90
1.39
1
3.93
0.88
1
MRC-100HWN1-R(C)
30.2
37.3
49.4
66×2
9.6×2
5.7×2
2
3.50
1.84
1
2.51
0.98
1
MRC-125HWN1-R(C)
41.5
52.9
66.4
64+139
8.3+16.6
4.75+9.16
2
4.84
2.03
1
3.66
0.83
1
MRC-150HWN1-R(C)
45.4
58.1
72.4
64+144
8.3+18.7
4.75+10.8
2
7.50
3.97
1
2.80
1.27
1
MRC-175HWN1-R(C)
55.2
72.7
88.4
139×2
16.6×2
9.16×2
2
6.60
3.03
1
3.53×2
0.80×2
2
MRC-200HWN1-R(C)
61.3
81.2
98.7
144×2
18.7×2
10.8×2
2
8.90
4.35
1
2.84×2
1.29×2
2
MRC-250HWN1-R(C)
74.7
93.4
116
158×2
20.66×2
12.1×2
2
9.70
4.40
1
3.71×2
2.07×2
2
MRC-300HWN1-R(C)
84.3
104.6
133.4
197×2
24.52×2
13.7×2
2
13.60
7.40
1
3.71×2
2.07×2
2
Notes:
MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A) MFA: Max. Fuse Amps (A)
STC: Starting Current (A); RNC: Running Current (A); IPT: Input Power (kW); Qty: Quantity
For 3Ph units, Voltage imbalance between each phases should be ˂2%.