Condenser coil
Unfiltered air circulates through the units condenser coil can cause the coils surface to become
clogged with dust. Clean the coil, vertically (i.e., with the fins), and stroke the coil surface with a soft
brush. Be sure to keep all vegetation away from the condenser coil area.
Periodic maintenance
To keep the unit operating safety and efficiently, the entire system should be checked at least once
each year. The examining the areas include:
Filter;
Motors and drive system components;
Economizer gaskets (Reserved);
Safety controls;
Electrical components and wiring (For possible replacement and connection tightness);
Condenser drainage (For cleaning);
Unit duct connections (To check that they are physically sound and sealed to the unit casing);
Unit mounting support (For structural integrity);
The unit (For obvious unit deterioration).
Appendix: - Temperature sensor
Room / Pipe temperature sensor Resistance Valve (R25 = 10 kOhm±1%, B25/50 = 4100K±1%)