9.4.3 The action of auto fan in fan-only mode is the same as auto fan in cooling mode with 24 setting temperature.
9.5 Cooling Mode
9.5.1 After starting, the operation frequency of compressor submits to following rule.
When the machine is running and ΔT(=room temp. – setting temp.) changes, the frequency of compressor will
rise or descend a grade (7 minutes after starting).
After starting, if ΔT stays in a zone for 3 minutes, the frequency will change as follow:
Zone A : Current frequency rise a grade till the maximum grade F8.
Zone B: Keep the current frequency of compressor.
Zone C: Descend the current frequency of compressor until F1.
Zone D: Compressor stops after running as the minimum frequency F1 for 60 minutes or ΔT is less than -2.
9.5.2 Indoor heat exchanger anti-freezing function.
If T2 is lower than 0, the compressor stops and resumes when T2>5.
9.5.3 Outdoor unit current control in cooling mode(refer to the parameter table)
9.5.4 Rating capacity test function
1) Set the indoor unit with remote controller as: high fan, 17 in cooling mode, then press “TURBO” button
D
-1.0
B
1.0
-0.5
0.5
1.5
C
T1 – 24
medium
3.5
3.0
1.5
1.0
high
low
I3COOL
I2COOL
I1COOL
comp. pause
freq. descends if curr. rises;
freq. remains if curr. descends
running normally
outdoor unit current
ΔT=(room temp) – (setting Temp)
A