Midea MS9A-09HRDN1-QC2 - 9.7 Heating Mode

Midea MS9A-09HRDN1-QC2
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
1) Anti-cold-wind function.
2) If the compressor stops caused by room temperature rising, indoor fan will be forced to run 127
seconds with breeze. During this period, anti-cold-wind is disabled. After this, anti-cold –wind function is
available.
3) If the machine runs in rating capacity test mode, indoor fan runs with rating speed, and
anti-cold-wind is disabled.
9.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is preferential.
Auto fan action in heating mode.
9.7.3 After start the operation frequency of compressor submits to following rule:
When the machine runs, if ΔTh stays in a zone for 3 minutes, action of frequency is as follow:
Zone A: Elevate the current frequency one grade, and not stop until the maximum grade.
Zone B: Keep the current frequency.
Zone C: Descend the current frequency one grade.
Remark: ΔTcon can be changed among 0, -2,- 4, the default is 0
A
5.0
4.5
3.0
2.5
D
C
ΔTh=(room temp) – (setting Temp) –ΔTcon
3.5
B
44
38
37
34
33
24
17
setting fan speed
low fan
breeze
super breeze
fan stop
Evaporator temp
ΔT=(room temp) – (setting Temp)
medium
2.5
2.0
1.5
1.0
low
high