12
5.5 MSE-12CR 
 
SUMMER      OUTDOOR TEMPERATURE DRY 
Indoor 
Conditions 
    25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 
Total capacity kW  3.38  3.21  2.99  2.75  2.52  2.35 
Sensitive capacity kW  2.53 2.28 2.18 2.07 1.96 1.88 
21ºC D 
15ºC W 
Input kW.  1.20 1.30 1.41 1.51 1.61 1.72 
Total capacity kW  3.62  3.46  3.26  3.06  2.86  2.68 
Sensitive capacity kW  2.50 2.42 2.34 2.25 2.19 2.16 
24ºC D 
17ºC W 
Input kW.  1.20 1.31 1.43 1.54 1.65 1.76 
Total capacity kW  3.88  3.80 
3.60 
3.32 3.02 2.76 
Sensitive capacity kW  2.71  2.65 
2.55 
2.42 2.30 2.19 
27ºC D 
19ºC W 
Input kW.  1.23  1.34 
1.45 
1.57 1.68 1.80 
Total capacity kW  3.95  4.01  3.95  3.82  3.64  3.46 
Sensitive capacity kW  2.56 2.59 2.57 2.53 2.50 2.51 
32ºC D 
23ºC W 
Input kW.  1.22 1.35 1.48 1.62 1.75 1.89 
 
 
 
5.6 MSE-12HR 
 
SUMMER      OUTDOOR TEMPERATURE DRY 
Indoor 
Conditions 
    25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 
Total capacity kW  3.38  3.21  2.99  2.75  2.52  2.35 
Sensitive capacity kW  2.53 2.28 2.18 2.07 1.96 1.88 
21ºC D 
15ºC W 
Input kW.  1.20 1.30 1.41 1.51 1.61 1.72 
Total capacity kW  3.62  3.46  3.26  3.06  2.86  2.68 
Sensitive capacity kW  2.50 2.42 2.34 2.25 2.19 2.16 
24ºC D 
17ºC W 
Input kW.  1.20 1.31 1.43 1.54 1.65 1.76 
Total capacity kW  3.88  3.80 
3.60 
3.32 3.02 2.76 
Sensitive capacity kW  2.71  2.65 
2.55 
2.42 2.30 2.19 
27ºC D 
19ºC W 
Input kW.  1.23  1.34 
1.45 
1.57 1.68 1.80 
Total capacity kW  3.95  4.01  3.95  3.82  3.64  3.46 
Sensitive capacity kW  2.56 2.59 2.57 2.53 2.50 2.51 
32ºC D 
23ºC W 
Input kW.  1.22 1.35 1.48 1.62 1.75 1.89