9
5. Capacity table
5.1 MSE-07CR
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 2.02 1.92 1.79 1.64 1.51 1.41
Sensitive capacity kW 1.44 1.39 1.34 1.27 1.20 1.15
21ºC D
15ºC W
Input kW. 0.70 0.76 0.82 0.88 0.95 1.00
Total capacity kW 2.16 2.07 1.95 1.83 1.71 1.60
Sensitive capacity kW 1.53 1.48 1.43 1.38 1.34 1.32
24ºC D
17ºC W
Input kW. 0.70 0.77 0.84 0.90 0.97 1.03
Total capacity kW 2.32 2.27
2.15
1.98 1.81 1.65
Sensitive capacity kW 1.65 1.62
1.56
1.48 1.41 1.34
27ºC D
19ºC W
Input kW. 0.72 0.79
0.85
0.92 0.99 1.05
Total capacity kW 2.36 2.39 2.36 2.28 2.18 2.07
Sensitive capacity kW 1.57 1.59 1.57 1.55 1.53 1.54
32ºC D
23ºC W
Input kW. 0.71 0.19 0.87 0.95 1.03 1.10
5.2 MSE-07HR
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 2.02 1.92 1.79 1.64 1.51 1.41
Sensitive capacity kW 1.44 1.39 1.34 1.27 1.20 1.15
21ºC D
15ºC W
Input kW. 0.70 0.76 0.82 0.88 0.95 1.00
Total capacity kW 2.16 2.07 1.95 1.83 1.71 1.60
Sensitive capacity kW 1.53 1.48 1.43 1.38 1.34 1.32
24ºC D
17ºC W
Input kW. 0.70 0.77 0.84 0.90 0.97 1.03
Total capacity kW 2.32 2.27
2.15
1.98 1.81 1.65
Sensitive capacity kW 1.65 1.62
1.56
1.48 1.41 1.34
27ºC D
19ºC W
Input kW. 0.72 0.79
0.85
0.92 0.99 1.05
Total capacity kW 2.36 2.39 2.36 2.28 2.18 2.07
Sensitive capacity kW 1.57 1.59 1.57 1.55 1.53 1.54
32ºC D
23ºC W
Input kW. 0.71 0.19 0.87 0.95 1.03 1.10