DM16-01.01.23en Kids Star Inverter
Service manual 43
11.2.5 Refrigerant Leakage Detection diagnosis and solution (PL)
Error Code
PL
Malfunction decision
conditions
Cooling mode:
25℃<T450
|ucT1Average-ucT2Average|coolantT0
|ucT2AveCompOpen- ucT2Average |coolantT2
| ucT1AveCompOpen - T1_Average| < 3
Heating mode:
T40
|T2Average_heat-T1_Average|heatantT0
|ucT2AveCompOpen - T2Average | heatantT2
| ucT1AveCompOpen - T1_Average| < 3
Supposed causes T2,T4,T1 sensor faulty
Indoor PCB faulty
System problems, such as leakage or blocking.
Trouble shooting:
Check air blowing out
from indoor air outlet
Yes
Yes
Check if T2,T1,T4
sensor is well fixed
No
Check leakage of system
No
Power off, then restart the
unit 2 minutes later.
Replace indoor PCB.
Yes
Repair the leakage and
recharge the refrigerant.
Yes
check blockIng of system and
clear the blocking