25
anti-cold-wind is disabled.
9.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is preferential.
Auto fan action in heating mode.
9.7.3 The operation frequency of compressor after starting submits to following rule:
When the machine runs, if ∆Th stays in a zone for 3 minutes, action of frequency is as follow:
Zone A: Elevate current frequency one grade, and not stop until the maximum grade.
Zone B: Elevate or keep or descend current frequency.
Zone H: Compressor stops after running with F1 for 60 minutes or when ∆Th>6℃.
9.7.4 Outdoor unit current control in heating mode.
Remark:
I1HEAT I2 HEAT I3 HEAT
9K Model 5.5 A 7.0 A 8.0A
12K Model 5.2 A 6.4 A 7.5 A
9.7.5 Indoor heat exchanger high temperature protection.
If T2>60℃, the compressor will stop and not resume until T2<48℃.
Remark: ∆Tcon can be changed among 0, -2,- 4 , the default is 0℃ ℃
H
B
℃
∆Th=(room temp) – (setting Temp) –∆Tcon
I3HEAT
I2HEAT
I1HEAT
comp. pause
freq. descends if curr. rises;
freq. remains if curr. descends
running normally
outdoor unit current
∆T=(room temp) – (setting Temp)
medium
2.5