EasyManua.ls Logo

Midea MTIU-18HWFNX-QRD0W - Capacity Correction Factor for Height Difference

Midea MTIU-18HWFNX-QRD0W
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Outdoor Unit 10
3. Capacity Correction Factor for Height Difference
Capacity(Btu/h) 12k Pipe Length (m)
Cooling 5 10 20 25
Height difference
H (m)
Indoor Upper
than Outdoor
10 0.973 0.948 0.936
5 0.995 0.983 0.958 0.945
0 1.000 0.988 0.963 0.950
Outdoor Upper
than Indoor
-5 1.000 0.988 0.963 0.950
-10 0.988 0.963 0.950
Heating 5 10 15 20
Height difference
H (m)
Indoor Upper
than Outdoor
10 0.993 0.978 0.970
5 1.000 0.993 0.978 0.970
0 1.000 0.993 0.978 0.970
Outdoor Upper
than Indoor
-5 0.992 0.985 0.970 0.962
-10 0.977 0.962 0.955
Capacity(Btu/h) 18k Pipe Length (m)
Cooling 5 10 20 30
Height difference
H (m)
Indoor Upper
than Outdoor
20 0.928 0.912
10 0.969 0.937 0.921
5 0.995 0.979 0.946 0.930
0 1.000 0.984 0.951 0.935
Outdoor Upper
than Indoor
-5 1.000 0.984 0.951 0.935
-10 0.984 0.951 0.935
-20 0.951 0.935
Heating 5 10 20 30
Height difference
H (m)
Indoor Upper
than Outdoor
20 0.982 0.976
10 0.994 0.982 0.976
5 1.000 0.994 0.982 0.976
0 1.000 0.994 0.982 0.976
Outdoor Upper
than Indoor
-5 0.992 0.986 0.974 0.968
-10 0.978 0.966 0.960
-20 0.959 0.953

Other manuals for Midea MTIU-18HWFNX-QRD0W

Related product manuals