110 Installation 
5.3 Concentrated drainage pipe 
5.3.1 Concentrated drainage piping diameter 
Select drainage pipe diameter according to indoor unit’s combined flow volume. 
E.g. If one 1HP unit with 2L/h condensation discharge, the calculation of the combined flow volume of three 
2HP units and two 1.5HP units is: 2HPx2L/hx3+1.5HPx2L/hx2 =18L 
5.3.2 Relation between horizontal piping diameter and permitted displacement of condensation 
Inner diameter of 
piping(reference value: (mm)) 
Inner diameter 
of piping (mm)) 
Permitted displacement(1/h) 
(Reference value)could not be 
used for confluence pipe 
Could be used for confluence 
pipe 
Attention: joints require PVC40 or larger piping. 
5.3.3 Relation between vertical piping diameter and displacement of condensation. 
Inner diameter of 
piping(reference value: (mm)) 
Inner diameter of 
piping (mm) 
Permitted 
displacement(1/h) 
(Reference value)could not be 
used for confluence pipe 
Could be used for confluence 
pipe 
Attention: joints require PVC40 or larger piping. 
5.3.4 Operation process of concentrated drainage 
Install indoor unit → connect drainage pipe → water pass test and overflow water test → thermal insulation of 
drainage pipe 
Caution: 
1) Increase drainage point as much as possible and reduce quantity of connected indoor units, to ensure 
horizontal main drainage pipe is not too long. 
2) Units with drainage pump and natural drainage shall have separate drainage systems.. 
3) Add two elbows at air outlet, and make sure its mouth faces down to prevent dirt from entering and creating 
blockages. 
 
 
5.4 Lifting of drainage pipe (for the unit with lift pump) 
Installation of lift pipe 
1. When connecting drainage pipe with indoor unit, use pipe clamp shipped with unit to fix. Glue splicing is not 
permitted for ensuring convenience in repairing. 
2. To ensure 1/100 slope, total lift height of drainage pipe (H) shall depend on indoor unit’s pump, and do not 
set vent pipe on the lifting pipe section. After lifting vertically, immediately place down inclined, otherwise it will 
cause error operation of switch at water pump. The connecting method is shown as follows: 
Gradient of drain pipe should be more than 1/100