R410A All DC Inverter V5 X Series 50Hz      MCAC-VTSM-2015-10 
124 Installation 
2. Inspection list of trial run: 
1)  Confirm  the  fan  impeller  is  rotating  according  to  its  intended  route  and  turns  smoothly.  No  abnormal 
vibration and noise. 
2) Check for abnormal noise during operation of refrigerant system and compressor. 
3) Confirm outdoor unit can detect each indoor unit. 
4) Confirm drainage is smooth and its lift pump is operational. 
5) Confirm microcomputer controller is operating normally and no warning indicators have been activated. 
6) Confirm operating current is within the allowed range. 
7) Confirm each operating parameter is within the range permitted by the equipment. 
Note: When conducting trial run, separately test cooling mode and heating mode to judge the stability and 
reliability of system. 
14.3.2 Commissioning for the trial run of multiple outdoor units 
1. Confirm operation of single unit  is  normal  through  trial  operation. After confirming  it  is normal, conduct 
operation of the whole system. 
2. Commissioning is carried out according to the Technical Requirement of Product. When Commissioning, 
analyze  and  record  operation  status  so  as  to  understand  the  operation  status  of  the  whole  system  for 
convenient maintenance and inspection. 
3. After finishing Commissioning, fill out Commissioning report in detail. 
14.4 Fill the name of connected system 
To clearly identify the connected systems among two or more indoor units and outdoor units, select names for 
every system and record them on the nameplate on the outdoor electric control box cover.   
 
14.5 Refrigerant leakage caution 
  This air conditioner adopts R410A as refrigerant, which is safe and noncombustible.   
  Air conditioned rooms should be large enough that if leakage occurs critical levels will not be reached, and 
time for protective measure can be ensured. 
  R410A critical thickness: 0.3 kg/m
3
, (Critical thickness: the max thickness of Freon without any harm to 
person) 
 
  Calculate the critical thickness through following steps, and take necessary actions. 
1. Calculate the refrigerant charge A 
Model(indoor unit)
Room Name
Eg: Indoor unit (A) of the
first system on second floor
is recorded as:-2F-1A
Outdoor unit
Indoor unit
Room full of leaking refrigerant
(All the refrigerant has leaked)