MCAC-VTSM-2015-10      R410A All DC Inverter V5 X Series 50Hz 
Installation                                                                                                                                                         95 
1. Select indoor unit pipes from indoor unit to the nearest branch joint: a, b, c, d, e, f, g, h, i, j, k, l, m.   
  Refer to table 5, the pipes of a, b, c, d, e, g, h, i, k, l, m are Φ15.9/ Φ9.53; the pipes of f and j are Φ12.7/ 
Φ6.35. 
2. Select the main pipe L1, indoor unit main pipes L2~L12 and branch joints A~L: 
  The downstream indoor units of L4 are N2 and N3, with total capacity of 140+71=211. Refer to table 1, the 
indoor unit main pipe L4 is Φ19.1/Φ9.53. The branch pipe assembly D is FQZHN-01D. 
  The downstream indoor unit of L3 is N1, N2 and N3, with total capacity of 140×2+71=351. Refer to table 1, 
the indoor unit main pipe L3 is Φ28.6/Φ12.7. The branch pipe assembly C is FQZHN-03D. 
  The downstream indoor unit of L6 is N5 and N6, with total capacity of 140+28=168. Refer to table 1, the 
indoor unit main pipe L6 is Φ19.1/Φ9.53. The branch pipe assembly F is FQZHN-01D. 
  The downstream indoor units of L5 are N4, N5 and N6, with total capacity of 140×2+28=308. Refer to table 1, 
the indoor unit main pipe L5 is Φ22.2/Φ9.53. The branch pipe assembly E is FQZHN-02D. 
  The downstream indoor units of L2 are N1, N2, N3, N4, N5 and N6, with total capacity of 140×4+71+28=659. 
Refer to table 1, the indoor unit main pipe L2 is Φ28.6/Φ15.9. The branch pipe assembly B is FQZHN-03D. 
  The downstream indoor unit of L10 is N9 and N10, with total capacity of 71+28=99. Refer to table 1, the 
indoor unit main pipe L10 is Φ15.9/Φ9.53. The branch pipe assembly J is FQZHN-01D. 
  The downstream indoor units of L9 are N8, N9 and N10, with total capacity of 140+71+28=239. Refer to 
table 1, the indoor unit main pipe L9 is Φ22.2/ Φ9.53. The branch pipe assembly I is FQZHN-02D. 
  The downstream indoor units of L8 are N7, N8, N9 and N10, with total capacity of 140×2+71+28=379. Refer 
to table 1, the indoor unit main pipe L8 is Φ28.6/Φ12.7. The branch pipe assembly H is FQZHN-03D. 
  The downstream indoor units of L12 are N12 and N13, with total capacity of 56×2=112. Refer to table 1, the 
indoor unit main pipe L12 is Φ15.9/Φ9.53. The branch pipe assembly L is FQZHN-01D. 
  The downstream indoor units of L11 are N11, N12 and N13, with total capacity of 140+56×2=252. Refer to 
table 1, the indoor unit main pipe L11 is Φ22.2/Φ9.53. The branch pipe assembly K is FQZHN-02D. 
  The  downstream  indoor  units  of  L7  are  N7,  N8,  N9,  N10,  N11,  N12  and  N13,  with  total  capacity  of 
140×3+71+56×2+28=631. Refer to table 1, the indoor unit main pipe L7 is Φ28.6/Φ15.9. The branch pipe 
assembly G is FQZHN-03D. 
3. Select main pipe L1 and branch joint A: 
  For outdoor units with capacity of 42HP, the equivalent length of all pipes in this system is larger than 90m, 
refer to table 2, the main pipe L1 is Φ38.1/ Φ22.2, the branch pipe assembly A is FQZHN-04D. 
  The downstream indoor units of L1 are N1~N13,  with total capacity of 140×7+71×2+56×2+28×2=1290. 
Refer to table 1, the indoor unit main pipe L1 is Φ38.1/Φ19.1. So we finally select the larger pipe Φ38.1/ 
Φ22.2 as main pipe L1. 
4. Outdoor unit connection pipe (g1, g2, g3, G1,L+M) selection (refer to table3, table 4) 
  The pipe g1 is connected to 12HP outdoor unit. Refer to table3, the diameter of g1 is Φ25.4 /Φ12.7. 
  The pipe g2 is connected to 12HP outdoor unit. Refer to table3, the diameter of g2 is Φ25.4 /Φ12.7. 
  The pipe g3 is connected to 18HP outdoor unit. Refer to table3, the diameter of g3 is Φ31.8/ Φ15.9. 
  Refer to table3, the diameter of G1 is Φ38.1/ Φ19.1. 
  The quantity of combined outdoor units is three. Refer to table4, the outdoor branch assembly is L+M: 
FQZHW-03N1D.