 Procedure 2.22.5
 
The inverter module heat sink is blocked 
or dirty 
Clean or replace the heat sink 
The screws connecting the heat sink to 
the inverter module are loose 
Tighten the screws and make sure the 
heat sink is well-connected 
Inverter module temperature sensor 
connection on main PCB is loose
1
 
Ensure the sensor is connected properly 
Inverter module temperature sensor has 
short circuited or failed
2
 
 
Notes:   
1.  Inverter module temperature  sensor  connection  is  port  CN3  and  CN3_1  on  the  main  PCB  (labeled 5  and  6,  respectively,  in  Figure  5-2.1  in  Part  5,  2.1 
“Ports”). 
2.  Measure  sensor  resistance.  If  the  resistance  is  too  low,  the  sensor  has  short-circuited.  If  the  resistance  is  not  consistent  with  the  sensor’s  resistance 
characteristics table, the sensor has failed. Refer to Table 6-3.3 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.