Midea V6-i Series Service Manual
 
6.4 Compressor and Inverter Module Protection Control 
This control protects the compressors from abnormally high currents and protects the inverter modules from abnormally 
high temperatures. It is performed for each compressor and inverter module. 
Figure 3-6.4: Compressor current protection control 
 
 
Figure 3-6.5: Inverter module temperature protection control 
Notes:   
1.  T
f
: Heat sink temperature 
 
6.5 Disable Heating Control 
When the  outdoor ambient  temperature rises  above  25°C heating mode is  disabled to prevent  the mechanical load on 
compressors becoming too high and to prevent low compression ratios which can result in insufficient compressor internal 
oil lubrication.   
Figure 3-6.6: Disable heating control 
   
When  PL  protection  occurs  3  times 
in  100  minutes,  the  C7  error  is 
displayed. When a C7 error occurs, a 
manual  system  restart  is  required 
before  the  system  can  resume 
operation. 
Compressor current protection, error code xP3 is displayed 
Compressor output reduced 
Inverter module temperature protection, 
error code PL is displayed 
Outdoor ambient temperature > 25
o
C 
Outdoor ambient temperature < 23
o
C