V6-i VRF 50/60Hz 
    51 
Table 4-1.1: Outdoor unit main PCB switch settings (continued) 
Auto addressing (default) 
Start-up time is 12 minutes (default) 
Start-up time is 7 minutes 
Use the new centralized controller (default) 
Use the old centralized controller 
Only 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C should be selected 
0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP; 5: 18HP; 6: 20HP; 7: 22HP; 8: 24HP; 
9: 26HP; A: 28HP; B:30HP; C:32HP 
Only 0, 1, 2, 3, 4, 5, 6, 7 should be selected (default is 0) 
The number of indoor units is in the range 0-15 
0-9 on ENC3 indicate 0-9 indoor units; A-F on ENC3 indicate 10-15 indoor units 
The number of indoor units is in the range 16-31 
0-9 on ENC3 indicate 16-25 indoor units; A-F on ENC3 indicate 26-31 indoor units 
The number of indoor units is in the range 32-47 
0-9 on ENC3 indicate 32-41 indoor units; A-F on ENC3 indicate 42-47 indoor units 
The number of indoor units is in the range 48-63 
0-9 on ENC3 indicate 48-57 indoor units; A-F on ENC3 indicate 58-63 indoor units 
Night silent time is 6h/10h (default) 
Night silent time is 6h/12h 
Night silent time is 8h/10h 
Night silent time is 8h/12h 
Silent mode 1 (only limit max. fan speed) 
Silent mode 2 (only limit max. fan speed) 
Silent mode 3 (only limit max. fan speed) 
Super silent mode 1 (limit max. fan speed and compressor frequency) 
Super silent mode 2 (limit max. fan speed and compressor frequency) 
Super silent mode 3 (limit max. fan speed and compressor frequency) 
Super silent mode 4 (limit max. fan speed and compressor frequency) 
Set silent mode via centralized controller (reserved) 
Notes: 
1.  Black denotes the switch position. 
2.  Refer to Part 4, 1.2.1 “Priority mode setting”. 
3.  Switch ENC2 is factory-set and its setting should not be changed. 
4.  Refer to Part 4, 1.2.2 “Silent mode setting”.