V6-i VRF 50/60Hz 
    93 
Part 
6 - Diagnosis and Troubleshooting
 
Notes:   
1.  Compressor  inverter module  address is  set through  dial switch S7  on the inverter  module.  The compressor inverter module  A/B  location  refers  to  the 
wiring diagram. 
 
0 for compressor inverter module A 
1 for compressor inverter module B 
 
2.  Communication wire from outdoor main PCB CN26 to inverter module CN8/CN9. 
Communication port CN26 on main PCB 
Communication port CN8/CN9 on inverter module 
3.  LED1/2 on inverter module 
 
4.  Check the power supply for the compressor inverter module, port CN41 on filter board, the normal voltage should be DC310V; check the high pressure 
switch  connection port  CN61  on  filter board,  the normal resistance should be  zero;  Check  the  single phase bridge  and  fuse  on  filter board;  check  the 
connection cable from ODU main PCB port CN82 to filter board port CN30 which is DC310V power control port. 
 
   
SMPS of 
Compressor inverter 
module 
CN61 High 
pressure switch 
connection port