VC Pro VRF 50/60Hz     
154     
Midea VC Pro Series Engineering Data Book 
Figure 3-4.2: Permitted refrigerant piping lengths and level differences   
 
 
 
 
 
 
 
Table 3-4.3: Summary of permitted refrigerant piping lengths and level differences 
L
1
 + 2 x Ʃ{L
2
 to L
16
} + Ʃ{a to q} 
Piping between farthest indoor 
unit and first outdoor branch 
joint
2
 
Piping between farthest indoor unit and first 
indoor branch joint
3
 
Piping between outdoor unit and outdoor branch 
joint 
g1+G1 ≤ 10m; g2+G1 ≤ 10m; 
g3 ≤ 10m 
Largest level difference between 
indoor unit and outdoor unit
4
 
Largest  level  difference  between  indoor  units
5
 
Notes: 
1.  Refer to Requirement 1, above. 
2.  Refer to Requirement 2, above. 
3.  Refer to Requirement 3, above. 
4.  Refer to Requirement 4, above. 
5.  Refer to Requirement 5, above. 
 
 
   
N1
(140)
N4(140)
N9
(112)
N10
(140)
N12
(28)
N13
(140)
N16
(56)
N15
(140)
N3(71)
N7(28)
N6
(140)
N8(140)
N14
(56)
N17
(140)
A
B
I
J
N
K
O
C
F
H
E
L1
L2
L3
L5
L7
L8
L11
L12
L13
L15
L14
L16
L9
a
c
d
f
g
h
j
l
m
n
o
p
q
k
S
R
g1
g2
g3
G1
D
N2
(140)
b
L4
N5
(112)
G
L6
e
N11
(71)
i
L
L10
M
P
W3
(16)
W2
(22)
W1
(26)
Largest level di
fference betwee indoor
unit and outdoor unit ≤ 90m
Piping between farthest indoor unit and first indoor
branch joint ≤ 40m
Equivalent length of piping between farthest indoor
unit and first outdoor branch joint ≤ 200m
ILargest level di
fference between
indoor units ≤ 30m
Figures in 
parentheses indicate 
indoor unit capacity 
indexes.