VC Pro VRF 50/60Hz 
    185 
Part 3 - System Design and Installation 
  Communication wiring for a multi outdoor unit system 
Figure 3-9.7: Communication wiring for a multi outdoor unit system   
  
 
10 Installation in Areas of High Salinity 
10.1 Caution 
Do not install outdoor units where they could be directly exposed to sea air. Corrosion, particularly on the condenser and 
evaporator fins, could cause product malfunction or inefficient performance. 
 
Outdoor units installed in seaside locations should be placed such as to avoid direct exposure to the sea air and additional 
anticorrosion treatment options should be selected, otherwise the service life of the outdoor units will be seriously affected.   
 
Air conditioning installed in seaside locations should be run regularly as the running of the outdoor unit fans helps prevent 
build-up of salt on the outdoor unit heat exchangers. 
 
10.2 Placement and Installation 
Outdoor units should be installed 300m or more from the sea. If possible, well-ventilated indoor locations should be chosen. 
(When installing outdoor units indoors, outdoor unit discharge ducts should be added. See Part 3, 3 “Outdoor Unit Ducting 
and Shielding”.) Refer to Figure 3-10.1. If it is necessary to install outdoor units outside, direct exposure to the sea air should 
be avoided. A canopy should be added to shield the units from sea air and rain, as shown in Figure 3-10.2. 
 
Ensure that base structures drain well so that outdoor unit footings do not become waterlogged. Check that outdoor unit 
casing drainage holes are not blocked. 
 
Figure 3-10.1: Installation in a well-ventilated indoor area 
Figure 3-10.2: Installation outdoors under a canopy