7.1.4 Installation of piping insulation 
With the exception of joint insulation, insulation should be applied to piping before fixing the piping in place. Insulation at 
joints in refrigerant piping should be applied after the gastightness test has been completed. 
 
 
7.1.5 Installation of joint insulation 
Insulation at joints in the refrigerant piping should be installed after the gastightness test has been successfully completed. 
The procedure at each joint is as follows: 
1.  Cut a section of insulation 50 to 100mm longer than the gap to be filled. Ensure that the cross-sectional and longitudinal 
openings are all cut evenly. 
2.  Embed the section into the gap ensuring that the ends abut tightly to the sections of insulation either side of the gap. 
3.  Glue the longitudinal cut and the joints with the sections of insulation either side of the gap. 
4.  Seal the seams with tape. 
   
Figure 3-7.1: Installation of joint insulation (unit: mm) 
Copper pipe
Insulation
material
400
300
straight-through joint
Insulation
material
 
7.2 Drain Piping Insulation 
  Use rubber/plastic insulating tube with a B1 fire resistance rating. 
  The insulation should typically be in excess of 10mm thick. 
  For drain piping installed inside a wall, insulation is not required. 
  Use suitable adhesive to seal seams and joints in the insulation and then bind with cloth reinforced tape of width not 
less than 50mm. Ensure tape is fixed firmly to avoid condensation. 
  Ensure the drain piping insulation adjacent to the indoor unit drainage water outlet is fixed to the unit itself using 
adhesive, to prevent condensation and dripping. 
 
7.3 Ducting Insulation 
  Suitable insulation should be added to ducting in according with all applicable legislation.   
  Installation of insulation should be carried out in a manner suited to the type of insulation material being used. 
  Ensure there are no gaps at the joints between sections of insulation. 
  Do not  apply tape too  tightly  as doing  so may  shrink insulation, reducing its  insulating properties  leading to 
condensation and loss of efficiency. 
  Insulate gas  and liquid  pipes separately,  otherwise  heat  exchange between  the two  sides will  greatly impact 
efficiency. 
  Do not bind the separately insulated gas and liquid pipes together too tightly as doing so can damage the joints 
between sections of insulation.