7 
 
 
  5 Electronic function(For remote 
control models) 
5.1 Terms and definitions 
  TA: Temperature of indoor ambient (T1) 
  TE: Temperature of evaporator (T2). 
  TC: Temperature of condenser (T3). 
  TO: Temperature of outdoor ambient (T4) 
  TS: The set temperature. 
  DAHT: Sensor of heater(T5) 
 
5.2 Protection function 
1. The compressor restart protection functions with a 
delay of 3 minutes. 
2. Sensor redundancy and automatic shutoff. 
5.3 Auto mode 
In Auto  mode,    the  unit  will  choose  cooling  or 
fan-only mode according to ΔT(ΔT =TA-Ts)   
5.4 Fan-only mode 
1. The temperature can’t  be  controlled  at  the  mode, 
and the room ambient temperature is display on LED. 
The temperature only display 32 to 99  ℉(0 to 37℃), lf 
out of range will display LO or HI. 
2. The Ion/ Timer functions are valid at the fan-only 
mode. 
3. Auto fan: In fan-only mode, AC operates the same 
as auto fan in cooling mode with the temperature set 
at 24°C(75°F). 
5.5 Cooling mode 
1. The temperature can be set from 62 to 86℉(17 to 
30℃) 
2. Compressor Control 
The compressor operates as below: 
(TA-Ts)℉
+2
0
Operation conditon 
compressor off with a delay of 1 minute
compressor on
 
When TA≤TS, compressor off 
When T1>TS+2℉, compressor on 
3. Fan Control 
In cooling mode, the indoor fan operates continuously.   
The fan speed can be set to high, medium or low. 
•  The auto fan acts as below rules: 
TA-TS(  F)
High
Medium
Low
2.5
-1
0
o
 
4. Auto-defrosting function protection as below: 
When TE is lower, it means that the evaporator frosts. 
Then  the  unit  starts  defrosting,  and  the  indoor  fan 
keeps working at the moment. When the temperature 
is up, the unit stops defrosting. 
TE ℉
55
30
compressor off 
when TE is lower than 30℉
lasting for 5 seconds
compressor on