58
★ 9 times
X
EH
0b/Eb
Indoor PCB/Display board communication error
——
★ 8 times
X
EE
Water-level alarm malfunction
——
★ 7 times
X
EC
Refrigerant leakage detection
——
★ 1 time
F0
Current overload protection
——
★ 2 times
F1
Outdoor ambient temperature sensor (T4 ) malfunction
E4
★ 3 times
F2
Condenser coil temperature sensor (T3) malfunction
E4
★ 4 times
F3
Compressor discharge temperature sensor (T5) malfunction
E4
★ 5 times
F4
Outdoor unit EEPROM parameter error
E0
★ 6 times
F5
Outdoor fan speed malfunction
E8
★ 7 times
F6
Indoor coil outlet pipe sensor(Located on outdoor unit low pressure
valve)
——
★ 8 times
F7
Communication malfunction between Cassette optional lift panel
and the unit.
——
★ 9 times
F8
Cassette optional lift panel malfunction
——
★ 10 times
F9
Cassette optional lift panel not closed
——
★ 11 times
FA
Communication error between indoor two chips(For A6 Duct)
——
★ 1 time
★
P0
Inverter module (IPM) malfunction
P6
★ 2 times
★
P1
Over-voltage or under-voltage protection
E5
★ 3 times
★
P2
High temperature protection of compressor top(OLP)/ High
temperature protection of IPM board
——
★4 times
★
P3
Low ambient temperature protection
LP
★ 5 times
★
P4
Compressor drive malfunction
——
★ 6 times
★
P5
(——)
Indoor units mode conflict
——
★ 7 times
★
P6
Low pressure protection
P2
★ flash , light, X extinguished
All Easy Pro type, Infini type
Operation lamp
Timer
lamp
Display
LED STATUS
ODU
Error
★ 1 time
X
EH
00/EH
0A
Indoor unit EEPROM parameter error
——
★ 2 times
X
EL 01
Communication malfunction between indoor and outdoor units
E2
★ 4 times
X
EH 03
Indoor fan speed malfunction
——
★ 6 times
X
EH 60
Indoor room temperature sensor (T1 ) malfunction
——
★ 6 times
X
EH 61
Evaporator coil temperature sensor (T2) malfunction
——
★ 1 time
★
PC 08
Current overload protection
——