Troubleshooting
Electrical Control System 189
2.4.4 Outdoor Units
2.4.4.1. Compressor Driven Chip EEPROM Malfunction
Malfunction conditions
Main PCB chip does not receive feedback from EEPROM chip
Possible causes
Installation mistakes
Faulty PCB
Yes
Replace the outdoor main
PCB
Replace the outdoor main
PCB
Power off, then restart the
unit 2 minutes later. Does the
malfunction still remain?
Power off, then restart the
unit 2 minutes later. Does the
malfunction still remain?
Compressor driven chip
EEPROM malfunction
Compressor driven chip
EEPROM malfunction