Troubleshooting
Electrical Control System 197
2.4.4.7. F4 Malfunction
Malfunction conditions
Main PCB chip does not receive feedback from EEPROM chip
Possible causes
Installation mistakes
Faulty PCB
Yes
Replace the outdoor main PCB
Replace the outdoor main PCB
Power off, then restart the
unit 2 minutes later. Does a
problem still exist?
Power off, then restart the
unit 2 minutes later. Does a
problem still exist?
Outdoor EEPROM malfunction
Outdoor EEPROM malfunction
F4- Display
F4- Display
EEPROM: An electrically erasable programmable read-only memory whose contents can be erased and
reprogrammed using a pulsed voltage.
2.4.4.8. F5 Malfunction
The same as E3 in indoor unit.