18 
Test capacitor.                                                                                                                                                                                         
Replace if not within +/-10% of manufacture's rating. 
Check bearings. Replace the motor if the blower wheel cannot 
rotate freely. 
Pay attention to any change from high speed to low speed. 
Replace the motor if the speed does not change. 
Compressor stops 
instantly after 
startup. 
The amount of the refrigerant is too much, making the 
compressor load too big. Recycle and recharge the refrigerant 
after checking for the reason. 
The compressor is blocked inside. Replace after checking for 
the reason. 
Check voltage at electrical outlet. Correct if none. 
Check and correct if water alarm happens. 
Check voltage at the power cord terminal on Main PCB. 
Replace the power cord if none. 
Transformer (Discharge 
transformer before testing) 
Check resistance between the two input/output lines on 
transformer. Replace the transformer if either of the 
input/output is open or the transformer is damaged. 
Wire disconnected or 
connection loose 
Connect wire. Refer to wiring diagram for terminal 
identification. Repair or replace loose terminal. 
Select fan speed and Check the voltage on main PCB. Replace 
the main PCB if no voltage in anyone. 
Capacitor (Discharge 
capacitor before testing) 
Test capacitor.                                                                                                                                                                                         
Replace if not within +/-10% of manufacture's rating. Replace if 
shorted, open or damaged. 
Fan blower hitting scroll. Realign assembly.                                                                                                                                                                                                 
Check fan motor bearings. Replace the motor if motor shaft do 
not rotate. 
Replace the fan blower if cracked, out of balance, or partially 
missing. 
Replace the motor if knocking sounds continue when running 
or loose, or the motor hums or noise appears to be internal 
while running. 
Compressor will 
not run while fan 
motor runs. 
Check voltage. Call Supply Authority if not within limits. 
Check the wire connections, if loose, repair or replace the 
terminal. If wires are off, refer to wiring diagram for 
identification, and replace. Check wire locations. If not per 
wiring diagram, correct. 
Check voltage of main PCB. Replace the main PCB if open. 
Capacitor (Discharge 
capacitor before testing) 
Check the capacitor.                                                                                                                                                                   
Replace if not within +/-10% of manufacturers rating. Replace 
if shorted, open, or damaged.   
Check the temperature setting if not at the coolest (in cooling 
mode) or the warmest (in heating mode). Set it if not.   
Check the compressor for open circuit or ground. If open or 
grounded, replace the compressor. 
Remove the cabinet and carefully rearrange tubing not to 
contact cabinet, compressor, shroud and barrier. 
Water depth is over load in 
chassis(P1) 
Use a drain hose and a pan to drain the condensed water in the 
chassis. 
Water depth sensor if 
failure 
Check and replace if failure. 
shaded pole motor failure 
Check and replace if the motor is failure. 
Cooling or heating 
feels not good 
Clean or replace if restricted. 
Realign and assemble if the installation of the air discharging 
pipe failure. Replace if damaged.