V6R VRF 50/60Hz
184
Midea
V6R
Series Engineering Data Book
V6R Series System Commissioning Report – Sheet E
table continued from previous page
Observed values
DSP1
content
Parameters displayed on DSP2
Remarks
Cooling
mode
Heating
mode
34.--
Static pressure mode
0: 0 Pa; 1: 20Pa; 2: 40Pa; 3: 60Pa; 4: 80Pa.
35.--
TES(°C)
Actual value = value displayed
36.--
TCS(°C)
Actual value = value displayed - 25
37.--
DC voltage A
Actual value = value displayed × 10
38.--
AC voltage B
Actual value = value displayed × 2
39.--
Number of indoor units for cooling operation
Actual value = value displayed
40.--
Number of indoor units for healing operation
Excluding HT hydro module
41.--
Number of high temperature HT hydro modules running
Actual value = value displayed
42.--
Total capacity of indoor units for cooling operation
43.--
Total capacity of indoor units for heating operation
Excluding HT hydro module
44.--
Total capacity of high temperature hydro modules running
45.--
Fan's failure history
46.--
Software version
47.--
Power limitation mode settings
48.--
Reserved
49.--
Reserved
50.--
Reserved
51.--
Most recent error or protection code
-- is displayed if no error or protection
events have occurred since start-up
-- --
--
End
Notes:
1. The fan speed index is related to the fan speed in rpm and can take any integer value in the range 1 (slowest) to 30 (fastest).
2. Silent mode:
0: night silent time 6h/10h; 1: night silent time 6h/12h; 2: night silent time 8h/10h; 3: night silent time 8h/12h; 4: no silent mode; 8: Silent; 10: Ultra-silent
Project name and location
System name