V6R VRF 50/60Hz
51
Table 2-7.2: MS box electrical characteristics
Model
Power Supply
1
Rated power
Hz
Volts
Min.
Max.
MCA
2
MFA
W
volts
volts
MS01
50
220~240
198
264
0.30
15
57
MS04
50
220~240
198
264
0.38
15
69
MS06
50
220~240
198
264
0.63
15
115
MS08
50
220~240
198
264
0.80
15
138
MS10
50
220~240
198
264
0.90
15
173
MS12
50
220~240
198
264
1.10
15
196
Notes:
1. Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
2. Select wire size based on the value of MCA.