P-10 enter "6", relay 1 - reset this value can be arbitrarily set
P-11 enter option "1", relay 2 - alarm function
P-12 enter "20", relay 2 - alarm ON
P-13 enter "19", relay 2 - alarm OFF
P-20 enter option "14", relay 5 - scanner
P-32 enter option "1", mA output on differential
P-68 enter "393.7", fill damping 393.7 in / min. Normally this level
would rise over a period of days or weeks,
therefore damping requirements would be fairly
slow. Typically, the factory set damping of 32.81
can be used.
P-69 enter "393.7", empty damping - same as fill damping
P-74 enter option "1, fail-safe high
P-75 enter "5", fail-safe timer
to re-enter run mode
RUN