P-29 pump run-on interval
the cyclical period in hours, in which a pump run-on duration may
occur. The initial interval begins upon return to the run mode or
resumption of power to the MultiRanger Plus. Subsequent intervals
begin at the end of the previous interval. Intervals end after the time
entered has expired or when the power or run mode is interrupted.
enter interval in hours ( F = - - - - )
P-30 pump run-on duration
the amount of time which the lead pump will continue pumping
after it has reached its OFF setpoint.
enter duration in seconds ( F = 0 )
P-31 spare
P-32 DLD milliamp output
when operating on the DLD mode, the milliamp output can be set to
correspond either to the differential or to the level under transducer #1
enter: 1 = differential ( F )
2 = level
P-33 inflow / discharge totaling
refer to Applications \ Pump Totalizer Application
enter: 1 = estimated inflow or discharge volume as added
to the pumped volume total ( F )
2 = estimated inflow or discharge volume is omitted
from the pumped volume total.
PL-443 7 – 6