How to resolve inverter reset issue on Mitsubishi Electric 700 Inverter?
- GGregory HillSep 14, 2025
To resolve an unexpected inverter reset on your Mitsubishi Electric Inverter, turn OFF the reset command.
How to resolve inverter reset issue on Mitsubishi Electric 700 Inverter?
To resolve an unexpected inverter reset on your Mitsubishi Electric Inverter, turn OFF the reset command.
What to do if Mitsubishi Electric 700 shows overcurrent trip during constant speed?
If your Mitsubishi Electric Inverter is tripping due to overcurrent during constant speed, try the following: * Ensure the load remains stable. * Inspect the wiring to rule out output short circuits or ground faults. * Reduce the setting of the stall prevention operation level. * Activate the fast-response current limit operation.
Why does Mitsubishi Electric Inverter show overcurrent trip during deceleration or stop?
If your Mitsubishi Electric Inverter experiences an overcurrent trip during deceleration or stop, consider the following: * Increase the deceleration time. * Check the wiring for output short circuits or ground faults. * Check the mechanical brake operation. * Lower the setting of stall prevention operation level. * Activate the fast-response current limit operation.
How to resolve inverter overload trip on Mitsubishi Electric 700 Inverter?
To resolve an inverter overload trip on your Mitsubishi Electric Inverter, consider the following: * Increase acceleration/deceleration time. * Adjust the torque boost setting. * Set the load pattern selection setting according to the load pattern of the using machine. * Reduce the load weight. * Ensure the surrounding air temperature is within specified limits.
What causes regenerative overvoltage trip during deceleration or stop in Mitsubishi Electric 700 Inverter?
A regenerative overvoltage trip during deceleration or stop on your Mitsubishi Electric Inverter can be addressed by: * Increasing the deceleration time. * Lengthening the brake cycle. * Using a brake resistor, brake unit, or power regeneration common converter (FR-CV) as needed.
How to resolve mode designation error on Mitsubishi Electric 700?
To resolve a mode designation error on your Mitsubishi Electric Inverter: * Set the operation mode to the "PU operation mode" before making parameter settings. * Alternatively, set Pr. 77 = "2" before making parameter settings.
How to clear maintenance signal output on Mitsubishi Electric 700 Inverter?
To clear the maintenance signal output on your Mitsubishi Electric Inverter, set "0" in Pr. 503 Maintenance timer. This erases the signal.
What to do if Mitsubishi Electric 700 Inverter shows write error during operation?
If your Mitsubishi Electric Inverter displays a write error during operation: * Set "2" in Pr. 77. * Alternatively, stop the operation before making parameter settings.
How to fix input phase loss on Mitsubishi Electric Inverter?
To fix an input phase loss issue on your Mitsubishi Electric Inverter: * Wire the cables properly. * Repair any breaks in the cable. * Check the Pr. 872 Input phase loss protection selection setting. * Set Pr. 872 = "0" (without input phase loss protection) when three-phase input voltage is largely unbalanced.
Why is my Mitsubishi Electric 700 heatsink overheating?
If your Mitsubishi Electric Inverter's heatsink is overheating: * Ensure the surrounding air temperature is within the specifications. * Clean the heatsink. * Replace the cooling fan.
Output Frequency | 400 Hz |
---|---|
Power Range | 0.4 to 15kW |
Overload Capacity | 150% for 60 seconds |
Control Method | V/f Control, Sensorless Vector Control |
Braking Unit | Built-in |
Communication | RS-485, Modbus RTU |
Protection Features | Overcurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault |
Protection Functions | Motor Overload |
Ambient Temperature | -10°C to +50°C (14°F to 122°F) |
Storage Temperature | -20°C to +65°C (-4°F to +149°F) |
Cooling Method | Forced air cooling |
Enclosure | Open type (IP20) |
Enclosure Rating | IP20 |
Rated Horsepower Range | 0.5 |