What does it mean when my Mitsubishi Electric FR-D700 displays electronic thermal relay function pre-alarm?
P
Patrick LoganSep 5, 2025
When your Mitsubishi Electric Inverter displays an electronic thermal relay function pre-alarm, it means the cumulative value of the electronic thermal O/L relay has reached 85% of the Pr. 9 Electronic thermal O/L relay setting or higher. To resolve this, reduce the load and frequency of operation or set an appropriate value in Pr. 9 Electronic thermal O/L relay.
L
Leah ClarkAug 25, 2025
What to do if my Mitsubishi Electric FR-D700 is showing overcurrent trip during constant speed?
A
Alexandra JohnsonAug 25, 2025
If your Mitsubishi Electric Inverter is showing an overcurrent trip during constant speed operation, make sure the load is stable. Also, check the wiring for any output short circuits or ground faults. Try lowering the stall prevention operation level and activating both the stall prevention operation and the fast-response current limit operation (Pr.156).
J
Jacob FritzAug 25, 2025
What to do if my Mitsubishi Electric FR-D700 shows overcurrent trip during deceleration or stop?
C
caroline69Aug 26, 2025
If your Mitsubishi Electric Inverter shows an overcurrent trip during deceleration or at a stop, try these steps: Increase the deceleration time. Check the wiring, looking for output short circuits or ground faults. Verify that the mechanical brake isn't activating too early. Also, consider lowering the stall prevention operation level and activating the stall prevention operation and the fast-response current limit operation (Pr.156).
D
Daniel PinedaAug 26, 2025
Why does my Mitsubishi Electric Inverter show an undervoltage error?
E
Emily RogersAug 27, 2025
An undervoltage error on your Mitsubishi Electric Inverter indicates that the voltage at the main circuit power supply has dropped. Investigate the devices on the power supply line, including the power supply unit itself, to find the cause.
C
Crystal MilesAug 27, 2025
What causes a stall prevention (overcurrent) on a Mitsubishi Electric Inverter and how to fix it?
M
Michael FoxAug 27, 2025
The overcurrent stall prevention on your Mitsubishi Electric Inverter has been activated. To resolve this:
* Increase or decrease the Pr. 0 Torque boost setting by 1% and check the motor status.
* Set a larger value in Pr. 7 Acceleration time and Pr. 8 Deceleration time.
* Reduce the load weight.
* Try General-purpose magnetic flux vector control.
* Adjust the Pr. 13 Starting frequency setting.
* Change the Pr. 14 Load pattern selection setting.
* Set the stall prevention operation current in Pr. 22 Stall prevention operation level.
T
Tina MartinezSep 13, 2025
How to unlock operation panel on Mitsubishi Electric FR-D700 Inverter?
K
Kaitlin GaySep 14, 2025
To release the lock on the operation panel of your Mitsubishi Electric Inverter, press for 2 seconds.
M
Maria MyersSep 12, 2025
What to do if my Mitsubishi Electric Inverter shows a safety stop?
S
susanmooreSep 12, 2025
If your Mitsubishi Electric Inverter indicates a safety stop (outputs are being shut off), and you are not using the safety stop function, short across terminals S1 and SC, and across S2 and SC with a shorting wire for the inverter to run. If is indicated when S1 and SC, and S2 and SC are both shorted while using the safety stop function (drive enabled), there may be an internal failure. Check the wiring of terminals S1, S2, and SC; if the wiring is correct, contact your sales representative.
B
Brandon LewisSep 12, 2025
What does 'PU stop' mean on a Mitsubishi Electric FR-D700?
J
James CookSep 12, 2025
If your Mitsubishi Electric Inverter displays 'PU stop', turn the start signal OFF and release with .
D
David ParrishSep 4, 2025
What causes a stall prevention (overvoltage) on a Mitsubishi Electric FR-D700?
B
barbara26Sep 4, 2025
The overvoltage stall prevention function on your Mitsubishi Electric Inverter has been activated. To resolve this, try setting a longer deceleration time.
R
Regina ReedSep 2, 2025
What does it mean when my Mitsubishi Electric FR-D700 shows a motor overload trip?
W
William EdwardsSep 2, 2025
A motor overload trip on your Mitsubishi Electric Inverter means the electronic thermal relay function for motor protection has activated. Try reducing the load. If you're using a constant-torque motor, set the constant-torque motor in Pr. 71 Applied motor. Adjust the stall prevention operation level accordingly.
Mitsubishi Electric FR-D700 Series Specifications
General
Series
FR-D700
Overload Capacity
150% for 60 seconds
Protection Class
IP20
Enclosure Rating
IP20
Communication
RS-485
Output Frequency
0.1 to 400 Hz
Control Method
V/f control, Vector control
Protection Functions
Overcurrent, Overvoltage, Undervoltage, Overload, Short circuit, Ground fault