Why is the total RMS value of harmonic current quite different from the current value on Mitsubishi Electric ME96SSH-MB?
- JJohn AdamsSep 2, 2025
The distortion ratio (content rate) is well over 100%. Check the measured item.
Why is the total RMS value of harmonic current quite different from the current value on Mitsubishi Electric ME96SSH-MB?
The distortion ratio (content rate) is well over 100%. Check the measured item.
Why does the backlight not light up on my Mitsubishi Electric ME96SSH-MB?
When it is set to auto off, it automatically goes off in 5 minutes. Use it as it is or change the setting to ON (Hold). For details, refer to 3.7.
How to fix a Mitsubishi Electric ME96SSH-MB Measuring Instruments display that does not light up?
Auxiliary power is not applied to MA and MB terminals. Apply auxiliary power supply.
Why does LOG light up but the clock status go off on Mitsubishi Electric ME96SSH-MB Measuring Instruments?
The present time is not set. Set the present time, and the clock status will light up. After this instrument restarts by applying the auxiliary power or by shifting from the test mode to the operating mode, the present time setting is necessary. For details, refer to 3.14Setting Menu CL: Preset Time Settings.
Why does the PASS 0000 display appear when clearing maximum, minimum values, or active energy on Mitsubishi Electric Measuring Instruments?
The password protection is enabled. Enter the password you set up. The factory default password is ‘0000.’ For details, refer to 5.2.18 Password Protection Setting.
What does the PASS 0000 display mean when entering the setting mode on Mitsubishi Electric Measuring Instruments?
The password protection is enabled. Enter the password you set up. The factory default password is ‘0000.’ For details, refer to 5.2.18 Password Protection Setting.
Why can't I change settings in the setting mode on Mitsubishi Electric ME96SSH-MB?
When blinks at the bottom left of the screen, it is in the setting confirmation mode. Therefore, setting change is not possible. Enter the setting mode to change settings.
Why are settings I have not altered changed on Mitsubishi Electric Measuring Instruments?
If you change a setting such as phase wire system, VT/Direct voltage, or CT primary current, some items will be reset to the default settings. Change the reset settings to your settings. For details, refer to 3.16 Initialization of Related Items by Changing a Setting.
Why do maximum and minimum values change on Mitsubishi Electric Measuring Instruments?
The values will be cleared if you change a setting such as phase wire system, VT/Direct voltage, or CT primary current. It is necessary to record the data before changing the setting.
Why is the active power displayed on my Mitsubishi Electric ME96SSH-MB different from the calculated value?
If the current and voltage AC waveforms distort due to harmonics, the displayed active power will differ from that calculated by multiplying the displayed current, voltage, and power factor. For current waveforms without harmonics, the calculated value matches the displayed value. You can continue to use the instrument as it is.
Product Name | ME96SSH-MB |
---|---|
Frequency | 50/60 Hz |
Communication | Modbus RTU |
Display | LCD |
Product Category | Power Meter |
Input Voltage | 100 to 240V AC |
Current Input | 1A/5A |