EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R04ENCPU - Return Bus Communication Error Count (Sub-Function Code: 0 CH)

Mitsubishi Electric MELSEC iQ-R04ENCPU
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 MODBUS STANDARD FUNCTION DETAILS
3.8 Diagnostics (FC: 08H)
29
3
Return bus communication error count (sub-function code: 0CH)
Operation description
Reads out the number of error messages detected on the line to the master.
Request message format (from master to slave)
Response message format (from slave to master)
When completed successfully
Returns the count value of the buffer memory listed below to the master.
'Bus communication error count' (Un\G32513/Un\G32577)
Refer to the following for the counter descriptions, count range, and count clear methods.
Page 21 Checking communication conditions using a diagnostic counter
When completed with an error
(H) (L)
08H (000CH) (0000H)
(H) (L)
DataFunction code Sub-function code
(H) (L)
(H) (L)
08H (000CH)
Function code Sub-function code
Bus communication
error count value
Data
(0000H to FFFFH)
88H
Data
Exception code
Function code

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-R04ENCPU

Related product manuals