2 PARAMETER SETTINGS
2.3 Application Settings
MODBUS/TCP Settings
Set MODBUS/TCP.
CPU Response Monitoring Timer
Set the time for monitoring the response from the CPU module.
When the CPU module does not send a response within the set time after the reception of a request message from the
MODBUS/TCP master device, the state of waiting for the response from the Ethernet-equipped module is canceled.
Set the CPU Response Monitoring Timer within the following range.
Item Description Setting range
To Use or Not to Use MODBUS/TCP
Setting
"Use" is displayed when a MODBUS/TCP connection device is added
in "External Device Configuration" under "Basic Settings". ("To Use or
Not to Use MODBUS/TCP Setting" cannot be edited.)
•Not Use
•Use
(Default: Not Use)
CPU Response Monitoring Timer Set the time for monitoring the response from the CPU module.
(Page 254 CPU Response Monitoring Timer)
Device Assignment Set the parameters to associate the MODBUS devices with the device
memory areas of the CPU module.
(Page 255 Device Assignment)
Unit Setting range
s 1 to 16383
ms 100 to 16383000 (in increments of 100ms)