Air-Conditioners For Building Application
Multiple Remote Controller Adapter PAC-SA88HA-E
Installation Manual
This installation manual describes only the connection of the Multiple Remote Controller Adapter to the outdoor unit of CITY MULTI air
conditioner series.
This part is a wiring member to connect the external circuit (locally procured) to the board on the indoor unit. This adapter has ports for the ON/
OFF signals, and error output status and operation status output can be checked.
For details of compatible models, connection method and setting method, refer to the CITY MULTI DATA BOOK, Electrical Wiring Diagram etc.
For your safety, first be sure to read section 1 "Safety Precaution" described below thoroughly and then install the PAC-SA88HA-E.
1. Safety Precaution
The following two symbols are used to denote dangers that may be caused by incorrect use.
WARNING
This symbol denotes what could lead to serious injury or death if you misuse the PAC-SA88HA-E.
CAUTION
This symbol denotes what could lead to a personal injury or property damage if you misuse the PAC-SA88HA-E.
After reading this manual, keep it in a place where the end user can find it anytime he or she wants to it. When someone moves, repairs or
uses the PAC-SA88HA-E, make sure that this manual is forwarded to the final user.
WARNING
Ask your dealer or technical representative to install the unit.
Any deficiency caused by your own installation may result in an electric
shock or fire.
Ensure that installation work is done correctly following this manual.
Any deficiency caused by installation may result in an electric shock or
fire.
Firmly connect the wiring using the specified cables.
Carefully check that the cables do not exert any forces on the
terminals.
Improper wiring connections may produce heat and possibly a fire.
Never modify or repair the PAC-SA88HA-E.
Any deficiency caused by your modification or repair may result in an
electric shock or fire. Consult with your dealer about repair.
All electrical work must be performed by a licensed technician,
according to local regulations and the instructions given in this
manual.
Any lack of electric circuit or any deficiency caused by installation may
result in an electric shock or fire.
Do not move and re-install the PAC-SA88HA-E yourself.
Any deficiency caused by installation may result in an electric shock or
fire. Ask your distributor or special vendor for moving and installation.
Stop the operation if any malfunction occurs.
If malfunction occurs (burning smell, etc.) stop the operation and turn off
the power supply. Contact your dealer or technical representative.
If the controller continues to operate after a malfunction occurs, this may
cause damage, electric shock or fire.
Do not turn on the main power until installation has been completed.
Doing so may result in electric shock or fire.
CAUTION
Do not install in any place exposed to flammable gas leakage.
Flammable gases accumulated around the body of PAC-SA88HA-E may
cause an explosion.
Do not use in any special environment.
Using in any place exposed to oil (including machine oil), steam and
sulfuric gas may deteriorate the performance significantly or give damage
to the component parts.
Wire so that it does not receive any tension.
Tension may cause wire breakage, heating or fire.
Do not install in any place at a temperature of more than 40°C
(104°F) or less than 0°C (32°F) or exposed to direct sunlight.
Do not install in any place where acidic or alkaline solution or
special spray are often used.
Doing so may cause an electric shock or malfunction.
Do not install in any steamy place such as a bathroom or kitchen.
Avoid any place where moisture is condensed into dew.
Doing so may cause an electric shock or malfunction.
Use standard wires in compliance with the current capacity.
A failure to this may result in an electric leakage, heating or fire.
Do not wash with water.
Doing so may cause an electric shock or malfunction.
2. Parts list
Make sure that the following items are included in the package.
Multiple Remote Controller Adapter 2 m (6-1/2 ft)
PAC-SA88HA-E: 1 pc.
3. Connection to the Indoor Unit
Connect the connector of the Multiple Remote Controller Adapter to the connector CN51 or CN52 of the indoor unit control board as necessary.
The connector can only be connected in one direction. Do not force the connection.
Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric PAC-SA88HA-E and is the answer not in the manual?

Mitsubishi Electric PAC-SA88HA-E Specifications

General IconGeneral
TypeAdapter
Power SupplyAC
Input Voltage220-240 V
CompatibilityMitsubishi Electric Air Conditioners
Input Frequency50 Hz
Output Frequency50 Hz
Operating Temperature-10 to +50 °C

Summary

Safety Precautions

Installation by Qualified Personnel

Emphasizes installation by a qualified technician to prevent electric shock or fire.

Proper Wiring and Connections

Ensures correct wiring and cable connections to prevent heat generation and fire.

Prohibition of Modification and Self-Repair

Warns against modifying or repairing the unit, advising consultation with a dealer.

Post-Installation Procedures

Advises against self-relocation and turning on power before installation is complete.

Malfunction Handling

Instructs to stop operation and cut power upon detecting malfunctions to prevent further damage.

Environmental Installation Restrictions

Lists environmental restrictions for installation, including gas, oil, steam, temperature, and chemicals.

Wiring Integrity and Material

Stresses wiring without tension and using standard wires to prevent breakage, heating, or leakage.

Water Exposure Prohibition

Prohibits washing the unit with water to prevent electric shock or malfunction.

Parts List

Included Components

Lists the items included in the package, such as the adapter and cable.

Connection to the Indoor Unit

Indoor Unit Connection Procedure

Details connecting the adapter's connector to the indoor unit's control board connector.

Locally Procured Parts

Required Locally Procured Parts

Lists parts that must be procured locally, depending on the connection method used.

Switch Specification

Specifies requirements for the single-pole, single-action switch, including low amperage contacts.

Relay Specification

Details specifications for the relay, including coil voltage, power consumption, and recommended diode.

Control Cable Specification

Outlines requirements for the control cable, including type, size, and extension limits.

Locally Procured Wiring

Wiring Examples for Indoor Units

Provides examples of basic connection methods for indoor units, referring to external data books.

CN51 Terminal Connections

Illustrates wiring for CN51, detailing input signals, standard pulses, and terminal functions for ON/OFF control.

CN52 Terminal Connections

Illustrates wiring for CN52, detailing output signals for status lamps and thermostat control.

Wiring Restrictions

Cable Length and Polarity Rules

Advises on cable length limits and correct polarity connection for relays to prevent damage.