Preparations in the field
Adapter
CN3D
2
1
3
X
Y
Brown
Red
X Y
SW1
SW2
Outdoor unit
control board
Maximum cable
length is 10 m
Orange
Power supply
of relay
X (SW1)
Y (SW2)
OPEN
SHORT
OPEN
100 %
0 % (Stop)
SHORT
75 %
50 %
* They are rough values.
2 Night mode (CN3D + DipSW4-7 OFF)
Outdoor unit
control board
Preparations in the field
Maximum cable
length is 10 m
Adapter
CN3D
2
1
3
X
Brown
Orange
Red
X
SW1
Power supply
of relay
Insulate this point securely as
this is not used.
X: Relay (Point of contact rating: DC1 mA)
Night mode: The noise level is reduced by limiting the
maximum fan frequency under the follow-
ing condition.
Cooling mode: outdoor temp. (TH6) < 30 °C
Heating mode: outdoor temp. (TH6) > 3 °C
X (SW1)
OPEN
SHORT
Night mode
OFF
ON
CAUTION
Do not install in any place where acidic or alkaline solution or
special spray are often used.
Doing so may cause an electric shock or malfunction.
Do not install in any steamy place such a bathroom or kitchen.
Avoid any place where moisture is condensed into dew.
Doing so may cause an electric shock or malfunction.
Use standard wires in compliance with the current capacity.
A failure to this may result in an electric leakage, heating or fire.
Do not wash with water.
Doing so may cause an electric shock or malfunction.
Air-Conditioners For Building Application
Remote ON/OFF <input> signal adapter PAC-SC36NA-E
Installation Manual
This installation manual describes only the connection of the Remote ON/OFF <output> signal adapter to the outdoor unit of PAC
air conditioner series.
This part is a wiring member to connect the external circuit (locally procured) to the board on the outdoor unit. Depending on the
connection, low level sound priority, power consumption, ON/OFF functions can be controlled.
For details of compatible models, connection method and setting method, refer to the outdoor unit service manual
.
For your safety, be sure to read firstly “ 1 Safety Precaution ” described below thoroughly and then install the PAC-SC36NA-E.
1 Safety Precaution
The following two symbols are used to denote dangers that may be caused by incorrect use.
WARNING
This symbol denotes what could lead to serious injury or death if your misuse the PAC-SC36NA-E.
CAUTION
This symbol denotes what could lead to a personal injury or property damage if you misuse the PAC-SC36NA-E.
After reading this instruction manual, keep it in a place where the end user can find it anytime he or she wants to it. When someone
moves, repairs or uses the PAC-SC36NA-E, make sure that this manual is forwarded to the final user.
WARNING
WT04936X01
Do not install in any place exposed to flammable gas leakage.
Flammable gases accumulated around the body of PAC-SC36NA-E
may cause an explosion.
Do not use in any special environment.
Using in any place exposed to oil (including machine oil), steam and
sulfuric gas may deteriorate the performance significantly or give
damage to the component parts.
Wire so that it does not receive any tension.
Tension may cause wire breakage, heating or fire.
Do not install in any place at a temperature of more than 40
°C
(104
°F) or less than 0 °C (32 °F) or exposed to direct sunlight.
All electrical work must be performed by a licensed technician,
according to local regulations and the instructions given in this
manual.
Any lack of electric circuit or any deficiency caused by installation
may result in an electric shock or fire.
Do not move and re-install the PAC-SC36NA-E yourself.
Any deficiency caused by installation may result in an electric shock or
fire. Ask your distributor or special vendor for moving and installation.
Stop the operation if any malfunction occurs.
If malfunction occurs (burning smell, etc.) stop the operation and
turn off the power supply. Contact your dealer or technical represen-
tative. If the controller continues to operate after a malfunction oc-
curs, this may cause damage, electric shock or fire.
Do not turn on the main power until installation has been com-
pleted.
Doing so may result in electric shock or fire.
GB
2 Parts list
Make sure that the following items are included in the package.
5 Locally Procured Wiring
Basic connection methods for following models are shown below as examples.
For details and the connection method with another models, refer to the CITY MULTI DATA BOOK, Electrical Wiring Diagram etc.
(1) PUHY, PUY, PURY-P200, 250, 300, 350YGM
PUHY, PURY-P400, 450, 500, 550, 600, 650YGM
PUHY-P700, 750, 800, 850, 900, 950, 1000, 1050, 1100, 1150, 1200, 1250YSGM
1 Step demand (CN3D + DipSW4-7 ON)
4 Locally Procured Parts
All parts other than the Remote ON/OFF <input> signal adapter (PAC-SC36NA-E) are procured locally.
The items required will depend on the connection method. Refer to the example of use shown below.
(Example)
1 External timer ....... No voltage contact out put timer (with separate circuits for power supply and switch).
2 Switch ................... Single pole, single action swich.
Ask your dealer or technical representative to install the unit.
Any deficiency caused by your own installation may result in an elec-
tric shock or fire.
Ensure that installation work is done correctly following this
instruction manual.
Any deficiency caused by installation may result in an electric shock
or fire.
Firmly connect the wiring using the specified cables.
Carefully check that the cables do not exert any forces on the
terminals.
Improper wiring connections may produce heat and possibly a fire.
Never modify or repair the PAC-SC36NA-E.
Any deficiency caused by your modification or repair may result in
an electric shock or fire. Consult with your dealer about repair.
Remote ON/OFF <input> signal adapter 3 m (9-3/4 ft) ...........1 pcs.
CAUTION: Choose the parts for the contact for minute electric current.
The timer and the contact of the switch will require degrees of 5 VDC, 12 V or 1 mA load. Choosing the wrong parts may cause
stoppage of the adapter.
3 Connection to the Outdoor Unit
Connect the connector side of the Remote ON/OFF <input> signal adapter to the connector CN3D, CN3N and CN3S of the outdoor unit
control board as necessary. The connector can only be connected in one direction only. Do not force the connection.
3 Transit relay .......... When the wiring work as described in
6. Wiring Restrictions
is required, this relay is used.
4 Control cable ........ The length of the electrical wiring for the PAC-SC37SA is 3 meters (9-3/4 ft).
To extend this length, use sheathed 2-core cable
Control cable type: CVV, CVS, CPEV or equivalent
Cable size: 0.5 mm
2
~ 1.25 mm
2
(16 to 22 AWG)
Dont extend the cable more than 10 meters (32 ft).
CAUTION:
1. Wiring should be covered by insulation tube with supplementary insulation.
2. Use relays or switches with IEC or equivalent standard.
3. The electric strength between accessible parts and control circuit should have 2750 V or more.
X, Y: Relay (Point of contact rating: DC1 mA)
Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric PAC-SC36NA-E and is the answer not in the manual?

Summary

Safety Precautions

Parts List

Connection to the Outdoor Unit

Locally Procured Parts

Special Functions

Low-Level Sound Priority Mode

Enables low-level sound priority mode by external signal input, reducing sound by 3-4 dB.

Demand Control ON;OFF Operation

Controls power consumption (0-100%) via external input, affecting compressor and fan operation.

Overview

The Mitsubishi Electric PAC-SC36NA-E is a remote ON/OFF signal adapter designed for use with Mitsubishi Electric PAC series air conditioners for building applications. This adapter serves as a crucial wiring component, facilitating the connection of external circuits (which must be locally procured) to the outdoor unit's control board. Its primary function is to enable external control over various operational aspects of the air conditioning system, including low-level sound priority, power consumption, and ON/OFF functions.

Function Description

The PAC-SC36NA-E adapter allows the air conditioning unit to receive external signals, which in turn can modify its operational behavior. One key function enabled by this adapter is the "Low-level sound priority mode." When an external signal is input to the outdoor unit via the adapter, the unit can operate with a reduced sound level, typically 3 to 4 dB lower than its usual operation. This mode is particularly useful in environments where noise reduction is critical. To activate this mode, a commercial timer or an ON/OFF switch contactor, connected to the CNDM connector on the outdoor controller board, sends a signal to the adapter. This setup allows for the control of the compressor operation frequency, which directly impacts the sound output. The effectiveness of this mode is dependent on the load and the conditioned outdoor temperature.

Another significant function is "Demand control" or "ON/OFF Operation." This feature allows for external input to manage the unit's power consumption. In this mode, the power consumption can be decreased within a range of 0% to 100% of the usual consumption. This is achieved by connecting a locally procured switch (SW1) between the Orange (1) and Red (3) terminals of the adapter. The brown lead wire should be insulated. Furthermore, the adapter works in conjunction with internal settings (SW7-1 and SW7-2) on the outdoor unit's control board to define specific power consumption levels. For instance, setting both SW7-1 and SW7-2 to OFF, while SW1 is closed, will stop the operation entirely (compressor and condensing fan stop), though the indoor fan may continue operating based on user settings. Other combinations of SW7-1 and SW7-2 allow for 50% or 75% power consumption when SW1 is closed. This demand control functionality is crucial for energy management and compliance with building energy regulations. It's important to note that while demand control can stop the compressor and outdoor fan, it does not override the functions of the wired controller for the indoor unit.

Usage Features

The PAC-SC36NA-E is designed for straightforward integration into existing Mitsubishi Electric PAC series air conditioning systems. The connection process involves plugging the adapter's connector into the CNDM connector on the outdoor unit's control board. The connector is designed to fit in only one direction, preventing incorrect installation.

For extending the control cable, standard sheathed 2-core cables are recommended, such as CVV, CVS, or CPEV, with a size ranging from 0.5 mm² to 1.25 mm² (16 to 22 AWG). The maximum extension length for the control cable is 10 meters (32 ft). This flexibility in cable length allows for versatile placement of external control devices.

When selecting locally procured parts, such as external timers or switches, it is critical to choose components designed for minute electric current loads. The timer and switch contacts should be rated for 5 VDC, 12 V, or 1 mA. Using incorrect parts can lead to the adapter malfunctioning. For applications requiring a transit relay, especially when specific wiring restrictions apply, a suitable relay must be used.

The installation manual emphasizes safety precautions, advising users to ensure that all electrical work is performed by a licensed technician in accordance with local regulations and the provided instructions. This ensures safe and correct operation, preventing electrical shocks or fire hazards. The manual also highlights the importance of firmly connecting wiring with specified cables, ensuring no tension is exerted on the terminals, which could lead to overheating or fire.

Maintenance Features

The PAC-SC36NA-E itself is not designed for user modification or repair. Any issues or malfunctions should be addressed by a dealer or technical representative. Attempting to modify or repair the unit can lead to electric shock or fire and will likely void any warranty.

In the event of a malfunction, such as a burning smell, users are instructed to immediately stop the operation and turn off the main power supply. Continuing to operate a malfunctioning unit can cause further damage, electric shock, or fire. Contacting a dealer or technical representative for repair is the recommended course of action.

The manual also provides guidelines for installation environments to ensure the longevity and proper functioning of the adapter. It advises against installation in places exposed to flammable gas leakage, as this could cause an explosion. Similarly, environments with oil (including machine oil), steam, sulfuric gas, or acidic/alkaline solutions can deteriorate performance or damage components. Installation in steamy places like bathrooms or kitchens, or where moisture condensation is likely, should also be avoided to prevent electric shock or malfunction.

Furthermore, the adapter should not be installed in places where the temperature is outside the range of 0 °C (32 °F) to 40 °C (104 °F) or exposed to direct sunlight. Wiring should be installed without tension to prevent breakage, heating, or fire. All wiring should be covered by insulation tubing with supplementary insulation, and relays or switches used must comply with IEC or equivalent standards. The electric strength between accessible parts and the control circuit should be at least 2750 V. These guidelines contribute to the overall safety and reliability of the system, minimizing the need for frequent maintenance.