SERVICE MANUAL
Notes:
• This manual describes ser-
vice data of 2 zone kit only.
PARTS CATALOG (OCB729)
2 ZONE KIT
[Model Name]
PAC-TZ02-E
[Service Ref.]
PAC-TZ02-E
November 2019
2 ZONE KIT
No. OCH729
CONTENTS
1. REFERENCE MANUAL ...........................2
2. SAFETY PRECAUTION ..........................3
3. SPECIFICATIONS....................................4
4. PARTS NAMES AND FUNCTIONS .........5
5. OUTLINES AND DIMENSIONS ...............6
6. WIRING DIAGRAM ..................................7
7. TROUBLESHOOTING .............................8
8. DISASSEMBLY PROCEDURE ................10

Other manuals for Mitsubishi Electric PAC-TZ02-E

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric PAC-TZ02-E and is the answer not in the manual?

Summary

Reference Manual

Safety Precautions for 2 Zone Kit

Specifications of PAC-TZ02-E

Parts Names and Functions

Component Parts Identification

Lists and illustrates the main components of the 2 zone kit.

Water Circuit and System Diagram

Diagrams the water flow and system connections for the 2 zone kit.

Outlines and Dimensions

Wiring Diagram and DIP Switch Settings

Troubleshooting Procedures

Self-Diagnosis and Error Code Procedures

Summary of self-diagnosis based on error codes and service procedures.

Test Run Preparation and Execution

Procedures and checks to perform before initiating a test run.

Remote Controller Malfunction Diagnosis

How to diagnose malfunctions using the main remote controller and error codes.

Component Functionality Checks

Methods to check the functionality of individual components like pumps and thermistors.

Disassembly Procedures for 2 Zone Kit

Front Panel Removal Guide

Step-by-step guide to detach the front panel of the 2 zone kit.

Mixing Valve Motor and Body Removal

Instructions for removing the mixing valve motor and body.

Water Pump Removal (Pump 2;3)

Steps to remove the water pumps (Pump 2 and Pump 3).

Reactor Removal Procedure

Procedure for removing the reactor components.

Thermistor Removal Guide

Guide to removing the thermistors for water temperature sensing.

Manual Air Vent Removal

Instructions for removing the manual air vent.

Quick Connection Detach;Attach

Steps for correctly attaching and detaching quick water connections.

Overview

This document serves as the service manual for the Mitsubishi Electric PAC-TZ02-E 2 Zone Kit, published in November 2019 (No. OCH729). It provides detailed information for installation, operation, troubleshooting, and maintenance of the 2 zone kit, specifically noting that it describes service data for the 2 zone kit only.

Function Description

The PAC-TZ02-E 2 Zone Kit is designed to work in conjunction with a cylinder unit (hydrobox), excluding E*SE models, to manage and distribute heating or cooling to two separate zones. This allows for independent temperature control in different areas, such as a radiator-based Zone 1 and a floor heating-based Zone 2. The kit integrates pumps, a mixing valve, and thermistors to regulate water flow and temperature for each zone.

The system's operation is governed by a control box within the cylinder unit (hydrobox), which interacts with the 2 zone kit components. DIP switch settings on the cylinder unit (hydrobox) are crucial for enabling and configuring 2-zone control, including settings for a mixing tank and 2-zone temperature control.

The circulator pumps within the 2 zone kit can operate in different pressure modes:

  • Proportional Pressure (PP): The head (pressure) is adjusted based on heat demand, reducing when demand falls and increasing when demand rises. This mode offers three curves (PP1, PP2, PP3) for varying pressure levels. The "PP Auto Adapt" function allows the circulator to automatically adjust its performance to the system size or load variations over time.
  • Constant Pressure (CP): The head (pressure) is maintained at a constant level regardless of heat demand. This mode also offers three curves (CP1, CP2, CP3) and a "CP Auto Adapt" function for automatic performance adjustment.
  • Constant Curve (CC): In this mode, the circulator runs on a constant curve, providing a consistent flow rate.

Important Technical Specifications

  • Model Name: PAC-TZ02-E
  • Dimensions (W × H × D): 265 x 383 x 383 mm
  • Weight: 17 kg
  • Power Supply: 230 V/single phase/50Hz from Cylinder unit (Hydrobox)
  • Sound Pressure Level: 28 dB(A)
  • Sound Power Level: 40 dB(A)
  • Pump2, 3: Max. 52 W/0.52 A, Max. head 7.0 m
  • Mixing Valve: 5 W, Running time 90° - 120 s
  • Water Flow Rate Range: Depends on the outdoor unit.
  • Max. Flow Rate: 36.9 L/min (exceeding this can cause pipe erosion).
  • Water Flow Rate Requirement: The water flow rate between the cylinder unit (hydrobox) and the 2 zone kit must be greater than the total flow rate of Zone1 and Zone2 to ensure proper heating.
  • Thermistor R0: 15 kΩ ±3%
  • B Constant: 3480 ±2%

Usage Features

  • Two-Zone Control: Provides independent temperature management for two distinct heating/cooling zones.
  • Flexible Operation Modes: Supports Proportional Pressure, Constant Pressure, and Constant Curve modes for circulator operation, allowing optimization based on system requirements.
  • Auto Adapt Function: Automatically adjusts pump performance to match system size or load variations in PP and CP modes, enhancing efficiency and comfort.
  • Integration with Hydrobox: Designed to seamlessly integrate with Mitsubishi Electric cylinder units (hydrobox) for a complete heating/cooling solution.
  • Safety Precautions: Emphasizes the importance of professional installation, adherence to local regulations, and proper electrical and plumbing connections to prevent water leakage, falls, or electrical hazards.
  • Test Run Procedure: Outlines steps for post-installation testing to ensure correct operation and safety.

Maintenance Features

  • Troubleshooting Guide: Includes a section for self-diagnosis based on error codes displayed on the main remote controller or control board. It advises referring to the cylinder unit (hydrobox) service manual for detailed solutions to error codes.
  • Component Checking: Provides instructions for checking the function of key components such as water circulation pumps, mixing valve, and thermistors. This includes verifying wiring, motor function, and resistance values for thermistors.
  • Disassembly Procedures: Detailed, step-by-step instructions with accompanying photos for disassembling various parts, including the front panel, mixing valve motor/body, water pumps, reactors, thermistors, and manual air vent.
  • Quick Connection Detachment/Attachment: Specific guidance on how to properly detach and attach quick connections, emphasizing the use of new O-rings and correct clip attachment to prevent leaks.
  • Draining Procedures: Comprehensive instructions for draining the cylinder unit and hydrobox, highlighting safety warnings regarding hot water and the need to isolate electrical supply. It also specifies parts where water may remain after draining, such as the strainer and pressure relief valve.
  • Tightening Torques: Specifies recommended tightening torques for gaskets (G1: 42 ± 2 Nm) and attached packing for the air vent (manual) (0.25 ± 0.05 Nm) during reinstallation, along with the requirement to use new O-rings or gaskets.
  • Parts Catalog: References a separate parts catalog (OCB729) for identifying and ordering replacement parts.

Mitsubishi Electric PAC-TZ02-E Specifications

General IconGeneral
BrandMitsubishi Electric
ModelPAC-TZ02-E
CategoryAir Conditioner Accessories
LanguageEnglish