EasyManuals Logo

Mitsubishi Electric PUHZ-RP100VHA2 User Manual

Mitsubishi Electric PUHZ-RP100VHA2
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #59 background imageLoading...
Page #59 background image
59
<Output pulse signal and the valve operation>
(2) Linear expansion valve operation
A
B
C
Open
Extra tightning (about 32 pulse)
Pulse number
500 pulse
Opening a valve
all the way
Close
Valve position (capacity)
Opening a valve : 8 7 6 5 4 3 2 1 8
Closing a valve : 1 2 3 4 5 6 7 8 1
The output pulse shifts in above order.
1. When linear expansion valve operation stops, all output phase
become OFF.
When the switch is turned on, 700 pulse closing valve signal will
be sent till it goes to
A point in order to define the valve position.
(The pulse signal is being sent for about 20 seconds.)
When the valve moves smoothly, there is no noise or vibration
occurring from the linear expansion valve : however, when the
pulse number moves from B to A or when the valve is locked,
more noise can be heard than normal situation.
No noise is heard when the pulse number moves from B to A in
case coil is burn out or motor is locked by open-phase.
Noise can be detected by placing the ear against the screw dri-
ver handle while putting the screw driver to the linear expansion
valve.
LEV
M
1
6
[4
[4
[3
[2
[1
2
1
Red
RP35-RP71
Brown
Blue
Orange
Yellow
White
3
4
5
6
Connector LEV-A
LEV-B
DC12V
Outdoor controller board
Drive circuit
[3
[2
[1
3
2
5
4
Linear expansion valve
(1) Operation summary of the linear expansion valve.
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the outdoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
1
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
[1
Output
(Phase)
Output
[2
[3
[4
234
5678
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
(RP35-RP71)
OC374A--2.qxp 06.7.26 5:54 PM Page 59

Other manuals for Mitsubishi Electric PUHZ-RP100VHA2

Questions and Answers: