13
OCH809A
4
DATA
4-1. REFILLING REFRIGERANT CHARGE (R32: kg)
4-2. COMPRESSOR TECHNICAL DATA
Service Ref.
PUZ-SWM60VAA.TR
PUZ-SWM80VAA.TR
PUZ-SWM100VAA.TR
PUZ-SWM120VAA.TR
PUZ-SWM80YAA.TR
PUZ-SWM100YAA.TR
PUZ-SWM120YAA.TR
PUZ-SWM140VAA.TR PUZ-SWM140YAA.TR
Compressor model DVB28FECMT DVB28FEDMT
DVB36FEAMT DVB36FEBMT
Winding
Resistance
(Ω)
U-V 0.94 0.94 0.32 0.94
U-W 0.94 0.94 0.32 0.94
W-V 0.94 0.94 0.32 0.94
(Winding temperature at 20°C)
Service Ref.
PUZ-SHWM60VAA
.TR
PUZ-SHWM80VAA
.TR
PUZ-SHWM100VAA
.TR
PUZ-SHWM120VAA
.TR
PUZ-SHWM80YAA
.TR
PUZ-SHWM100YAA
.TR
PUZ-SHWM120YAA
.TR
PUZ-SHWM140VAA
.TR
PUZ-SHWM140YAA
.TR
Compressor model DVK28FECMT DVK28FEDMT DVK36FEAMT DVK36FEBMT
Winding
Resistance
(Ω)
U-V 0.94 0.94 0.32 0.94
U-W 0.94 0.94 0.32 0.94
W-V 0.95 0.94 0.32 0.94
Heating only
Initial
amount
Chargeless
piping
length
Permitted
piping
length
Permitted
vertical
difference
Piping
length
2 to 3 m -5 m -10 m -15 m -20 m -25 m -30 m -35 m -40 m -45 m -50 m
Max.
amount
PUZ-
S(H)WM60/80/100*AA 1.80 kg 35 m -50 m -30 m
Total
amount, kg
1.30
*2
1.40
*2
1.50
*2
1.60
*2
1.70
*2
1.80 2.00 2.10 2.20
2.20 kg
Additional
charge
amount, kg
- - - - - - - - +0.20 +0.30 +0.40
S(H)WM120/140*AA 1.80 kg 30 m -50 m -30 m
Total
amount, kg
1.50
*2
1.60
*2
1.70
*2
1.80 1.80 2.00 2.20 2.30 2.40
2.40 kg
Additional
charge
amount, kg
- - - - - - - +0.20 +0.40 +0.50 +0.60
Reversible
(Cooling and Heating)
Initial
amount
Chargeless
piping
length
Permitted
piping
length
Permitted
vertical
difference
Piping
length
2 to 3 m -5 m -10 m -15 m -20 m -25 m -30 m -35 m -40 m -45 m -50 m
Max.
amount
PUZ-
S(H)WM60/80/100*AA 1.80 kg 15 m -50 m -30 m
Total
amount, kg
1.70
*2
1.80 1.80 1.90 2.00 2.10 2.20 2.30 2.40
2.40 kg
Additional
charge
amount, kg
- - - - +0.10 +0.20 +0.30 +0.40 +0.50 +0.60
S(H)WM120/140*AA 1.80 kg None.
*1
-30 m -30 m
Total
amount, kg
2.20 2.30 2.40
2.40 kg
Additional
charge
amount, kg
+0.40 +0.50 +0.60
*1 The piping length of 5 m is usable if the cases below are allowable.
•The maximum cooling capacity may drop over 20 percent. In this case, cooling efficiency will be less and the input increases as well.
•The running-water noise may occur from the extended pipings of the indoor unit.
*2 These values are recommended only in the case of recharging. At the initial installment, an adjustment for the amounts of refrigerant is not necessary.
*3 When setting the water temperature to 60°C or higher, add the refrigerant amount for the "reversible" even when using the "heating only".
Otherwise, the system may not operate due to the refrigerant shortage.