'19 • PAC-SM-309
-
99
-
E1
Remote control
communication circuit error
Keepsashing
Stays OFF
Keepsashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Is it possible to
reset normally by the
power reset?
Does the drain
pump restart automatically
1 minute later?
YES
YES
NO
Note (1) Only indoor unit
with drain pump
Turn SW7-1 to OFF. ON
Remove the wire
connecting
between indoor/outdoor units.
Connect the wire connecting
between indoor/outdoor units.
Power source reset
NO
1
Malfunction by noise
Check peripheral
environment.
Defective indoor unit control
PCB
Replace.
Move to E5.
(Communication error
during operation) check.
2. Error detection method
When normal communication
between the remote control and
the indoor unit is interrupted
for more than 2 minutes.
(Detectable only with the
remote control)
3 .
Condition of error displayed
Same as above
4. Presumable cause
Defective communication
circuit between remote
control-indoor unit
• Noise
Defective remote control
Faulty indoor unit control PCB
Note:
If the indoor unit cannot communicate normally with the remote control for 180 seconds, the indoor unit PCB starts to reset
automatically.
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDC140VSA-W and is the answer not in the manual?

Mitsubishi Heavy Industries FDC140VSA-W Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDC140VSA-W
CategoryAir Conditioner
LanguageEnglish

Related product manuals